NEC 314.16 · Box fill

How to calculate box fill with NEC 314.16

What counts, what doesn’t, and how many cubic inches you need — the counting rules in plain language with two worked examples and a free link to the official tables.

Need the actual tables? Look up 314.16 and Tables 314.16(A) and (B) in the free NFPA viewer →

What counts toward box fill (314.16(B)) — in our words

Item in the boxHow many allowancesSized by
Each conductor that enters from outside and terminates or is spliced1 eachThat conductor’s size
Conductor passing through unbroken1That conductor’s size
Unbroken conductor looped/coiled (long enough to be cut into two free ends)2That conductor’s size
Pigtails / jumpers that never leave the box0
Internal cable clamps (one or many)1 totalLargest conductor in the box
Luminaire studs or hickeys1 for each typeLargest conductor in the box
Each device yoke/strap (switch, receptacle)2 per yokeLargest conductor connected to that device
Device wider than a single 2-in. gang2 per gang it needsLargest conductor connected to it
Equipment grounding conductors (all of them)1 totalLargest EGC in the box
Up to four small fixture wires from a domed luminaire canopy (plus an EGC)0Allowed to be omitted under the listed conditions

Our own summary, not the code text (2023 NEC). Look up 314.16 and Tables 314.16(A) and (B) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ.

How to run a box-fill calc, step by step

StepWhat you doWatch out for
1List every item in the box using the counting rules aboveCount per yoke for devices, not per device — a duplex receptacle is one yoke
2Find the volume allowance for each conductor size in Table 314.16(B)Allowances are per conductor size, not per insulation type
3Multiply each count by its allowance and add them upItems sized by "largest conductor" use the largest one present, not an average
4Get the box volume: marked volume on the box, or Table 314.16(A) for standard metal boxesPlastic and non-standard boxes: use the marked volume — the table only covers standard metal boxes
5Add any marked volume from plaster rings, extension rings, or raised coversOnly if the ring or cover is marked with its volume (or listed in the table)
6Box volume must be at least the calculated totalIf it isn’t, go deeper, go to a 4-in. square with a ring, or add an extension

Our own summary, not the code text (2023 NEC). Look up 314.16 and Tables 314.16(A) and (B) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ.

Worked example 1 — receptacle box, two 12/2 NM cables with ground, internal clamps

ItemCountAllowanceVolume
Insulated 12 AWG conductors (2 per cable)42.25 in³9.00 in³
Internal cable clamps12.25 in³2.25 in³
Duplex receptacle (one yoke)22.25 in³4.50 in³
All EGCs together12.25 in³2.25 in³
Total required818.00 in³

12 AWG = 2.25 in³ per Table 314.16(B). The box (plus any marked ring) must be marked at 18.0 in³ or more. Worked-example values only — not the table.

Worked example 2 — switch box, two 14/2 NM cables with ground, no internal clamps

ItemCountAllowanceVolume
Insulated 14 AWG conductors42.00 in³8.00 in³
Single-pole switch (one yoke)22.00 in³4.00 in³
All EGCs together12.00 in³2.00 in³
Pigtail from ground splice to switch0
Total required714.00 in³

14 AWG = 2.00 in³ per Table 314.16(B). Many nonmetallic boxes have no internal clamps — count the clamp allowance only if clamps are inside the box. Worked-example values only.

Common field mistakes

MistakeWhat to do instead
Counting each ground wire separatelyAll EGCs together count as one allowance, sized by the largest
Counting a device as oneEach yoke counts as two, sized by the largest conductor connected to that device
Counting pigtailsWires that start and end inside the box don’t count
Using the Table 314.16(A) volume for a plastic boxUse the volume marked on the box — the table is for standard metal boxes
Forgetting the plaster ring or mud ring volumeA marked ring adds volume; an unmarked one adds nothing
Counting a clamp allowance for external connectorsOnly clamps inside the box count — connectors outside the box don’t

Our own summary, not the code text (2023 NEC). Look up 314.16 and Tables 314.16(A) and (B) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ.

📋 Embed this chart on your site — freeGet the code →

Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.

<iframe src="https://www.field-pm.com/embed/charts/nec-box-fill-rules" title="Box Fill Rules (NEC 314.16) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe>
<p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nec-box-fill-rules" target="_blank" rel="noopener">Box Fill Rules (NEC 314.16)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>

Box fill is a counting problem

Look up 314.16 and its tables in the free NFPA viewer. NFPA offers free read-only access to current NEC editions. This page explains how to use the rules (2023 NEC); it does not reproduce the tables.

Two tables, one comparison. Table 314.16(A) gives the volume of standard metal boxes (and the max number of same-size conductors they hold). Table 314.16(B) gives a volume allowance per conductor, by size. Everything else in 314.16(B) is a counting rule that converts clamps, devices, fittings, and grounds into conductor allowances. Add them up and the box has to be at least that big.

The counting rules in one breath. Each wire coming in that terminates or splices counts one; a wire passing through counts one (two if it is looped long enough to cut into two free ends); pigtails that never leave the box count zero. All internal clamps together count one. Each type of luminaire stud or hickey counts one. Each device yoke counts two, sized by the biggest wire on that device. All equipment grounding conductors together count one, sized by the largest. Clamps and fittings are sized by the largest conductor in the box.

Where the volume comes from. Standard metal boxes can use the table; anything else — plastic boxes, most specialty boxes — uses the volume marked in the box. Plaster rings, extension rings, and raised covers add their marked volume. That’s why a 4-in. square box with a deep ring can often solve a fill problem without changing the rough-in.

Worked example. A receptacle box with two 12/2 NM cables and internal clamps: 4 insulated conductors + 1 for clamps + 2 for the receptacle + 1 for all grounds = 8 allowances. At 2.25 in³ each for 12 AWG, the box needs 18.0 in³. A switch box on 14 AWG with no internal clamps is 7 × 2.00 in³ = 14.0 in³.

Skip the math with the free box fill calculator. For raceway fill instead of box fill, see the conduit fill chart and the conduit fill calculator; for conductor sizing, the NEC 310.16 ampacity chart. Field PM keeps rough-in photos and inspection sign-offs with the job.

FAQ

How do you calculate box fill?+

Count every conductor that enters and terminates or splices, add one allowance for all internal clamps, one for each type of luminaire stud or hickey, two for each device yoke, and one for all equipment grounding conductors. Multiply each count by the Table 314.16(B) volume for its conductor size, add them up, and compare with the box volume. Look up the tables free at nfpa.org/freeaccess.

How many cubic inches per 12 AWG and 14 AWG wire?+

Table 314.16(B) allows 2.25 in³ for each 12 AWG and 2.00 in³ for each 14 AWG conductor. Look up other sizes in the free NFPA viewer.

Do ground wires count in box fill?+

Yes — but all of them together count as a single allowance, based on the largest equipment grounding conductor in the box.

Why does a receptacle count as two conductors?+

Each device yoke or strap takes up space where wires would otherwise go, so 314.16(B)(4) assigns it a double allowance based on the largest conductor connected to it. A device too wide for a single 2-in. gang counts double for each gang it needs.

Does a pigtail count toward box fill?+

No. A conductor that originates in the box and never leaves it — like a splice-to-device pigtail — is not counted.

Built by a contractor, for the field

Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.

Start free trial →

More reference charts

Rated by contractors on

Field PM reviews on CapterraField PM reviews on GetAppField PM reviews on Software Advice