Quick reference · Wire size for a breaker

Wire Size & Breaker Chart

What gauge copper or aluminum wire pairs with a 15 to 100 amp breaker — the common 75°C sizes electricians reach for, with the NEC caveats that actually matter.

BreakerCopperAluminumTypical use
15 A14 AWG12 AWGLighting & general-purpose receptacles
20 A12 AWG10 AWGKitchen, bath, laundry, small-appliance circuits
30 A10 AWG8 AWGElectric water heater, dryer, small A/C
40 A8 AWG6 AWGElectric range, larger A/C
50 A6 AWG4 AWGRange, EV charger, small sub-panel
60 A4 AWG3 AWGSub-panel feeder, large A/C
70 A4 AWG3 AWGSub-panel feeder
80 A3 AWG2 AWGSub-panel feeder
90 A2 AWG1 AWGFeeder
100 A1 AWG1/0 AWG100 A sub-panel or feeder

Common copper/aluminum sizes at 75°C terminations. Exact size depends on termination temperature rating, continuous load (125% rule), ambient/conductor-count derating, and voltage drop — verify against NEC Table 310.16 and 240.4. Dwelling services/feeders may use smaller conductors under NEC 310.12 (e.g., 100 A = #4 Cu, 200 A = 2/0 Cu).

Matching wire size to a breaker

The breaker protects the wire, so the conductor must be able to carry at least the breaker's rating. This chart shows the common copper and aluminum sizes at 75°C terminations for the breakers you see most on residential and light-commercial work.

Three things move the answer off this chart: a continuous load (3+ hours) requires sizing conductor and breaker at 125% of the load; the termination temperature rating of the breaker/lug (often 60°C for small equipment) can require a larger conductor; and long runs may need an upsize for voltage drop. Always confirm against the full ampacity chart (310.16).

Check a long run with the voltage drop calculator, and size the raceway with the conduit fill calculator. Field PM keeps the panel schedules and inspection records together so the install matches the design.

FAQ

What size wire for a 50 amp breaker?+

A 50 A circuit is commonly wired with 6 AWG copper or 4 AWG aluminum at 75°C terminations. For a continuous 50 A load (on for 3+ hours) the conductor and breaker must be sized at 125%, which can push you to a larger conductor — always verify against NEC 310.16 and 240.4.

What size wire for a 100 amp sub-panel?+

A 100 A feeder is commonly 1 AWG copper or 1/0 AWG aluminum at 75°C. Dwelling services and feeders may use smaller conductors under NEC 310.12 — for example, 4 AWG copper or 2 AWG aluminum for a 100 A dwelling service.

Is this chart code?+

It reflects common 75°C copper/aluminum sizing, but the exact conductor depends on the termination temperature rating, continuous load (the 125% rule), ambient and conductor-count derating, and voltage drop. Use it as a quick reference and confirm with NEC Table 310.16 and 240.4(D).

Why does aluminum need to be a size larger?+

Aluminum has lower conductivity than copper, so for the same ampacity it must be roughly one to two AWG sizes larger — for example, 6 AWG copper and 4 AWG aluminum both carry about 50–65 A at 75°C.

Built by a contractor, for the field

Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.

Start free trial →