Free conduit fill calculator · NEC Chapter 9 · No signup
Pick a conduit type and size, add your THHN/THWN conductors, and get the fill percentage versus the NEC 53% / 31% / 40% limit — with a clear pass or fail.
Dimensions from manufacturer/ANSI data; results are close to NEC Chapter 9 tables but not a substitute — verify with your adopted edition. Fill limits per NEC Chapter 9, Table 1.
Paste this where you want the live calculator to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/free/conduit-fill-calculator" title="Conduit Fill Calculator — Field PM" width="100%" height="640" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/free/conduit-fill-calculator" target="_blank" rel="noopener">Conduit Fill Calculator</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
NEC Chapter 9, Table 1 sets the maximum percentage of a raceway's area that conductors may occupy: 53% for one conductor, 31% for two, and 40% for three or more. The limits exist so conductors can be pulled without damaging insulation and so bundled heat can dissipate.
The math: sum each conductor's cross-sectional area and divide by the conduit's internal area (which varies by type — EMT, IMC, RMC, PVC Sch 40/80). This tool works both areas out as π/4 × diameter² from manufacturer and ANSI dimension data (stranded copper THHN/THWN-2; EMT, IMC, RMC and PVC inside diameters) rather than copying the NEC tables. Compare to the limit for your conductor count. Every conductor counts, including neutrals and equipment grounds.
Getting this right at design avoids a failed inspection and a re-pull. Field PM keeps your panel schedules, submittals, and QA/QC records together in the job book so the rough-in matches the plan. For non-THHN insulations, use the dimensions in NEC Chapter 9 of your adopted edition or the wire manufacturer's data sheet.
Per NEC Chapter 9, Table 1: one conductor may fill up to 53% of the conduit's internal area, two conductors up to 31%, and three or more up to 40%. This calculator applies the right limit automatically based on how many conductors you enter.
Add up the cross-sectional area of every conductor and divide by the raceway's internal area, then compare the result to the 53% / 31% / 40% limit for your conductor count. This tool works each area out as π/4 × diameter², using conductor outside diameters from a THHN manufacturer spec sheet and raceway inside diameters from manufacturer/ANSI dimension data. The NEC's own Chapter 9 dimension tables govern — results here land close to them, but verify with your adopted edition.
It uses stranded copper THHN/THWN-2 — by far the most common building wire — with diameters from a manufacturer spec sheet. Other insulations (XHHW, RHW, USE) are thicker or thinner; for those, use the dimension table in NEC Chapter 9 of your adopted edition or the wire manufacturer's data sheet.
Yes. Every conductor in the raceway counts toward fill, including equipment grounding conductors and neutrals. Add them as rows here.
The percentages come from heat dissipation and the practical ability to pull conductors without damaging insulation. More conductors means more bundled heat and friction, so the allowable fill drops from 53% (one) to 40% (three or more).
Field PM builds the math into the platform — job costing, billing, and forecasting from real field data. 30-day free trial, no credit card.