NEC 250.122 · Equipment grounding explained

How to size the equipment grounding conductor with NEC 250.122

Size by the breaker, not the wire — plus the proportional-upsizing, parallel-run, and motor-circuit rules that trip up inspections, with worked examples.

Need the actual numbers?

This page teaches you how to use NEC Table 250.122 — it deliberately does not reproduce the table. Look up Table 250.122 in the free NFPA 70 (NEC) online viewer (free NFPA account, read-only), or your printed code book (Article 250, Part VI).

Section numbers and values vary by NEC edition, and your jurisdiction may adopt an older edition or local amendments. The edition your AHJ enforces governs.

How to read Table 250.122, step by step

StepWhat you do
1. Identify the OCPDFind the rating of the breaker or fuse on the supply side of the circuit — the device that will have to clear a ground fault. Not the load current, not the wire size.
2. Find the rowTable 250.122 rows are "not exceeding" ratings. Go down the first column to the first row that is equal to or greater than your device rating.
3. Read the material columnRead the copper column or the aluminum / copper-clad aluminum column for the EGC material you are installing.
4. Apply the table footnoteThe footnote reminds you that the EGC may need to be larger than the table to meet the fault-clearing requirement of 250.4(A)(5) / (B)(4) — usually a long-run or high-fault-current issue.
5. Apply 250.122(A)–(F)Cap at the circuit conductor size (A); increase proportionally if the phase conductors were upsized (B); use the per-raceway rule for parallel runs (F); motor circuits use the motor short-circuit device rating (D).
6. Confirm the EGC typeIf a raceway or cable armor is serving as the EGC, check 250.118 — some flexible wiring methods only qualify within length and OCPD limits.

Worked examples

ExampleInputsStepsResult
A. 100 A feeder, no upsizingCopper conductors sized for ampacity, 100 A breaker.Row for devices not exceeding 100 A, copper column: 8 AWG Cu per Table 250.122.8 AWG Cu EGC
B. 20 A circuit upsized for voltage drop20 A breaker; 12 AWG Cu would carry the load, but 10 AWG Cu was pulled for voltage drop.Table minimum for 20 A is 12 AWG Cu. Area ratio of phase conductors: 10,380 cmil ÷ 6,530 cmil ≈ 1.59. Required EGC ≥ 6,530 × 1.59 ≈ 10,380 cmil (250.122(B)).10 AWG Cu EGC
C. Parallel feeder in two conduitsTwo parallel sets, one per conduit, one breaker protecting both.Each conduit gets its own EGC sized from the full breaker rating — do not divide by the number of sets (250.122(F)).Full-size EGC in each conduit

Table values are quoted only to illustrate the calculation. Circular-mil areas are the standard AWG conductor areas. Look up your own rating in the official table for your adopted edition.

Which rule applies?

SituationWhere to look
Ordinary branch circuit or feederTable 250.122 by the OCPD rating
Phase conductors upsized (voltage drop, future load, etc.)250.122(B) — increase the EGC by the same circular-mil ratio
Parallel sets in separate raceways or cables250.122(F) — a full-size EGC in each raceway, based on the OCPD protecting the whole set (not divided)
Motor branch circuit250.122(D) — based on the rating of the motor short-circuit/ground-fault device, not the overload
Multiple circuits sharing one raceway250.122(C) — one EGC sized for the largest OCPD of the circuits it serves
Service or separately derived system bonding to earthNot an EGC question — that is the grounding electrode conductor (Table 250.66) or supply-side bonding jumper (250.102(C))

Common field mistakes

MistakeWhat to do instead
Sizing the EGC from the phase conductor sizeThe table is keyed to the overcurrent device. Start there.
Upsizing phases for voltage drop but not the EGC250.122(B) — grow the EGC by the same area ratio. A frequent inspection write-up.
Splitting the EGC across parallel racewaysEach raceway needs a full-size EGC per 250.122(F).
Using Table 250.66 for an equipment ground250.66 is for grounding electrode conductors. Mixing up EGC and GEC is the classic grounding error.
Sizing a motor EGC from the overloadUse the motor short-circuit/ground-fault device rating (250.122(D)).
Relying on flex as the ground without checking limitsFlexible metal conduit and some fittings only count as the EGC within the length and OCPD limits of 250.118 — otherwise pull a wire-type EGC.

What changed between editions

EditionWhat to know
2020 NEC250.122(B) was reworded to tie the proportional increase to conductors increased beyond the minimum size that has sufficient ampacity for the installation — clarifying how upsizing interacts with correction and adjustment factors.
2023 NECKept Table 250.122 and the 250.122(A)–(F) structure. Check the edition's change markers for revisions to the (B) wording and its exceptions.
2026 NEC and laterBeing adopted state by state — confirm the table and subsection letters in the edition your AHJ enforces.

Orientation only — confirm in the edition your jurisdiction has adopted.

📋 Embed this chart on your site — freeGet the code →

Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.

<iframe src="https://www.field-pm.com/embed/charts/equipment-grounding-conductor-chart" title="Sizing the EGC (NEC 250.122) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe>
<p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/equipment-grounding-conductor-chart" target="_blank" rel="noopener">Sizing the EGC (NEC 250.122)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>

When you need Table 250.122

The equipment grounding conductor (EGC) is the path that carries fault current back to the source so the breaker trips fast. Every branch circuit and feeder that needs one is sized from NEC Table 250.122, keyed to the rating of the overcurrent device ahead of the equipment.

The table is the minimum. The rules in 250.122(A) through (F) then modify it: never larger than the circuit conductors, proportionally larger when phases are upsized, full size in every parallel raceway, and motor circuits sized from the short-circuit device.

Grounding the service to earth is a different conductor — see the grounding electrode conductor (250.66) guide. For the phase conductors, see how to read NEC Table 310.16, and check long runs with the voltage drop calculator. Field PM keeps panel schedules, equipment lists, and inspection records together on the job.

FAQ

What size equipment grounding conductor for a 100 amp breaker?+

Per NEC Table 250.122, a circuit protected by a 100 A overcurrent device needs at least an 8 AWG copper equipment grounding conductor — unless the phase conductors were upsized, in which case 250.122(B) requires a proportional increase. For other ratings, look up Table 250.122 in the free NFPA viewer at nfpa.org/freeaccess.

Is the equipment grounding conductor sized by breaker or by wire size?+

By the rating of the overcurrent device (breaker or fuse) ahead of the equipment — not by the size of the ungrounded conductors. Two qualifiers: per 250.122(A) the EGC never has to be larger than the circuit conductors, and per 250.122(B) it must be increased proportionally if the ungrounded conductors are increased.

Do I upsize the ground wire if I upsize the conductors for voltage drop?+

Yes. When ungrounded conductors are increased above the minimum size needed for ampacity, 250.122(B) requires the EGC to be increased by the same ratio of circular-mil area. Example: going from 12 AWG to 10 AWG phase conductors on a 20 A circuit is a ratio of 10,380 ÷ 6,530 ≈ 1.59, so the 12 AWG EGC must grow to at least 10 AWG.

What is the difference between an EGC and the grounding electrode conductor?+

The equipment grounding conductor (EGC, Table 250.122) bonds equipment back to the source so faults trip the breaker; it is sized by the overcurrent device. The grounding electrode conductor (GEC, Table 250.66) connects the system to the earth electrode (rods, concrete-encased electrode, water pipe) and is sized by the service or derived-system conductor size. Different conductor, different table.

Built by a contractor, for the field

Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.

Start free trial →

More reference charts

Rated by contractors on

Field PM reviews on CapterraField PM reviews on GetAppField PM reviews on Software Advice