NEC 220.84 · 220.102 · 220.103 · 2023 NEC
Whether the building qualifies, what goes into each unit’s connected load, how the demand factor is picked, where house loads go — plus farm load demand under 220.103. Worked examples and a free link to the official tables.
Need the actual tables? Look up Tables 220.84 and 220.103 in the free NFPA viewer →
| Check | What to confirm | If it fails |
|---|---|---|
| Unit count | Three or more dwelling units on the feeder or service being calculated | Use the standard method (Part III), or 220.82 for a single unit |
| One feeder per unit | No dwelling unit is supplied by more than one feeder | Use the standard method |
| Electric cooking | Each unit has electric cooking equipment | Check the exception in 220.84(A) — it compares against a calculated cooking allowance |
| Electric heat or A/C | Each unit has electric space heating, air conditioning, or both | Use the standard method |
Our own summary of the 2023 NEC, not the code text. Look up 220.84, Table 220.84, 220.102, and Table 220.103 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice — service sizing is the designer of record’s call.
| Step | What you do | Watch out for |
|---|---|---|
| 1 | For one unit, list the connected load: general lighting at the dwelling VA per sq ft, small-appliance and laundry circuits, nameplate of fastened-in-place appliances, ranges, dryers, water heaters | Everything goes in at nameplate — no Table 220.55 or 220.53 demand here |
| 2 | Add the larger of the heating or air-conditioning load | Do not add both — only the larger |
| 3 | Multiply by the number of units (or total each unit type separately if they differ) | Sum every unit on the feeder or service |
| 4 | Find the demand factor in Table 220.84 by the number of units | The factor keeps dropping as the unit count grows |
| 5 | Multiply the total connected load by that factor | This is the dwelling-unit portion only |
| 6 | Add house loads (hall lighting, elevators, pumps, site lighting) calculated by the standard Part III method | House loads do not get the Table 220.84 factor |
| 7 | Calculate the neutral separately under 220.61 | The optional method sizes the ungrounded conductors |
Our own summary of the 2023 NEC, not the code text. Look up 220.84, Table 220.84, 220.102, and Table 220.103 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice — service sizing is the designer of record’s call.
| Input / step | Value | Source |
|---|---|---|
| Lighting: 1,000 sq ft × 3 VA | 3,000 VA | 220.84(C) |
| Two small-appliance + one laundry circuit | 4,500 VA | 220.84(C) |
| Range 12,000 + dryer 5,000 + water heater 4,500 VA (nameplate) | 21,500 VA | 220.84(C) |
| Larger of heat (10,000 VA) or A/C (5,000 VA) | 10,000 VA | 220.84(C) |
| Connected load per unit | 39,000 VA | Sum |
| Three units | 117,000 VA | × 3 |
| Demand factor for three units | 45% | Table 220.84 |
| Dwelling-unit demand load | 52,650 VA ÷ 240 V ≈ 219 A | Before house loads |
Worked example values only. Add the house loads at the standard method, then size the service. Look up the other unit-count rows in the free NFPA viewer.
| Level | Rule | What it does |
|---|---|---|
| Each farm building or load group (not the dwelling) | 220.102 / Table 220.102 | Sizes the feeder to each building: loads that run together at full value, the balance reduced in steps |
| The whole farm service | 220.103 / Table 220.103 | Ranks the building loads largest to smallest and applies a falling demand percentage to each |
| Loads with the same function in different buildings | 220.103 | May be combined and treated as a single load in the ranking |
| Farm dwelling | Dwelling methods (Part III or IV) | Calculated on its own — check how your edition combines it at a shared service |
Our own summary of the 2023 NEC, not the code text. Look up 220.84, Table 220.84, 220.102, and Table 220.103 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice — service sizing is the designer of record’s call.
| Input / step | Value | Source |
|---|---|---|
| Barn feeder load, after its own demand | 100 A | 220.102 |
| Shop/shed feeder load, after its own demand | 60 A | 220.102 |
| Largest load at 100% | 100 A | Table 220.103 |
| Second largest at 75% | 45 A | Table 220.103 |
| Farm equipment load at the service | 145 A | Sum |
| Farm dwelling | Calculated separately by the dwelling method | 220.102(A), 220.103 |
Worked example values only. The third-largest and remaining loads step down further — look up Table 220.103 in the free NFPA viewer.
| Mistake | What to do instead |
|---|---|
| Applying Table 220.55 range demand inside a 220.84 calc | The optional method takes ranges at nameplate — the table factor covers the diversity |
| Adding both heat and A/C | Only the larger of the two |
| Applying the Table 220.84 factor to house loads | House loads are calculated separately by the standard method and added |
| Using 220.84 on a gas-cooking building without checking the exception | Read 220.84(A) — it compares against a calculated cooking allowance |
| Counting the farm dwelling in the Table 220.103 ranking | Calculate the dwelling with the dwelling methods |
Our own summary of the 2023 NEC, not the code text. Look up 220.84, Table 220.84, 220.102, and Table 220.103 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice — service sizing is the designer of record’s call.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/nec-multifamily-optional-calculation" title="Multifamily Optional Calc (NEC 220.84) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nec-multifamily-optional-calculation" target="_blank" rel="noopener">Multifamily Optional Calc (NEC 220.84)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Look up 220.84 and Table 220.84 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how the method works; it does not reproduce the tables. Written to the 2023 NEC — verify against the edition your AHJ has adopted.
Why use it. The standard method stacks separate demand factors for lighting, ranges, dryers, and appliances. The optional method in 220.84 takes almost everything in each unit at nameplate, adds it up, and applies one demand factor based on the number of units. On all-electric apartment buildings it usually produces a smaller — and still code-compliant — service than the standard method.
The qualifying conditions are strict. Three or more units, no unit fed by more than one feeder, electric cooking in every unit (with an exception for buildings that don’t have it), and electric heat or air conditioning in every unit. Miss one and you are back to the standard method. House loads — corridors, elevators, fire pump, parking lot lights — are calculated with the standard method and added on top.
Farms work in two layers. 220.102 sizes the feeder to each barn, shop, or pump load group, taking the loads that run together at full value and reducing the balance. 220.103 then ranks those building loads at the service and takes each one at a falling percentage — full value for the largest, less for the second, and so on. The farm dwelling is calculated separately with the dwelling methods.
Build the per-unit load from the general lighting load guide and the cooking appliance demand guide. Then size service conductors with the NEC 310.16 ampacity chart, the OCPD from the standard breaker sizes guide, check long feeders with the voltage drop calculator, and lay out each unit on the panel schedule template.
When the building has three or more dwelling units, no unit is supplied by more than one feeder, and each unit has electric cooking and electric space heating, air conditioning, or both. There is an exception in 220.84(A) for buildings without electric cooking. Look up 220.84 in the free NFPA viewer at nfpa.org/freeaccess.
By the number of dwelling units on the feeder or service. The factor gets smaller as the count goes up — a three-unit building is taken at 45% of connected load. Look up the other rows in the free NFPA viewer.
Common-area loads such as hall lighting, elevators, pumps, and site lighting are calculated with the standard method in Part III and added to the demand-factored dwelling load. They do not get the Table 220.84 factor.
Each farm building is first calculated under 220.102. At the service, 220.103 ranks those loads from largest to smallest, takes the largest at 100% and the second largest at 75%, and reduces the rest further. The farm dwelling is calculated separately with the dwelling methods.
220.84, 220.102, and 220.103 kept their numbers through the 2023 reorganization of Article 220, and the methods are the same in principle. Check the edition your AHJ enforces for wording changes in the qualifying conditions and exceptions.
Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.
Start free trial →