IBC 601 / 602 / 716 · Fire ratings
Construction type sets the element ratings, fire separation distance sets the exterior wall ratings, and the wall rating sets the door rating. Here is how to read Tables 601, 602 and 716.1(2).
Need the actual tables? Read IBC Tables 601, 602 and 716.1(2) in the free ICC viewer →
| Question on the job | Table | Read it by |
|---|---|---|
| How many hours does the frame, bearing wall, floor or roof need? | Table 601 | Construction type column × building-element row |
| How many hours does this exterior wall need? | Table 602 (and the higher of it and 601) | Fire separation distance row × occupancy group column |
| Are openings allowed in this exterior wall, and how many? | Section 705 (exterior wall openings table) | Fire separation distance and whether openings are protected or sprinklered |
| What rating does the door, frame or glazing in this rated wall need? | Table 716.1(2) (doors), 716.1(3) (windows) | Type of wall assembly × wall rating |
| How do I build a rated assembly? | UL / listed design referenced on the drawings | The listing, not the IBC table |
Our own summary, not the code text. Read Tables 601, 602 and 716.1(2) free at codes.iccsafe.org and verify against the IBC edition (2021, 2024 or local amendment) adopted by your AHJ.
| Step | What you do | Watch out for |
|---|---|---|
| 1 | Confirm the construction type on the code sheet | Table 601 has a column per type — IA through VB, with the mass-timber IV types |
| 2 | In Table 601, read the rows for primary frame, bearing walls, nonbearing walls, floor and roof | The footnotes can reduce roof ratings or allow sprinklers to substitute in some cases |
| 3 | Find the fire separation distance for each exterior wall — measured to the lot line, street centerline, or an imaginary line between buildings | FSD is measured perpendicular to the wall face, not diagonally to the lot corner |
| 4 | In Table 602, read the row for that FSD and the column for the occupancy group; an exterior bearing wall must meet the higher of 601 and 602 | Ratings usually drop as distance grows — a wall near the lot line may need a rating the type alone would not |
| 5 | For each rated wall with a door or window, find the wall type and rating in Table 716.1(2)/(3) | Fire barriers, fire partitions, smoke barriers and exterior walls each have their own rows |
| 6 | Match the labels on doors, frames and glazing to the required rating | The whole assembly — door, frame, hardware, glass — must be listed for the rating |
Our own summary, not the code text. Read Tables 601, 602 and 716.1(2) free at codes.iccsafe.org and verify against the IBC edition (2021, 2024 or local amendment) adopted by your AHJ.
| Input / step | Value | Source |
|---|---|---|
| Construction type | IIA (noncombustible, protected) | Code sheet |
| Required rating for the primary structural frame | 1 hour | Table 601, IIA column |
| What that means in the field | Spray fireproofing or a listed board system at the thickness the UL design calls for | Drawings / listing |
| Corridor wall (fire partition) rating on the life-safety plan | 1 hour (as designed) | Drawings |
| Door rating in a 1-hour corridor fire partition | 20 minutes, self-closing and latching | Table 716.1(2) |
Worked example values only. Look up the full tables in the free ICC viewer.
| Mistake | What to do instead |
|---|---|
| Assuming the wall rating equals the door rating | Opening protectives are usually rated lower than the wall — use Table 716.1(2) |
| Measuring fire separation distance to the neighbor’s building | Measure to the lot line (or street centerline, or an imaginary line between buildings on one lot) |
| Patching fireproofing with the wrong product or thickness | Follow the listed design; get the fireproofing inspector to sign off before cover-up |
| Penetrating a rated wall without a listed firestop system | Match each penetration to a tested system (Section 714) and photo-document it |
| Installing an unlabeled frame or lite in a rated opening | Check labels on delivery — a missing label is a failed inspection |
Our own summary, not the code text. Read Tables 601, 602 and 716.1(2) free at codes.iccsafe.org and verify against the IBC edition (2021, 2024 or local amendment) adopted by your AHJ.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/ibc-fire-resistance-ratings" title="Fire-Resistance Ratings (IBC 601/602/716) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/ibc-fire-resistance-ratings" target="_blank" rel="noopener">Fire-Resistance Ratings (IBC 601/602/716)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Read Tables 601, 602 and 716.1(2) in the free ICC digital codes viewer. ICC offers free read-only access to the I-Codes. This page explains how the tables relate under the 2021 and 2024 IBC; it does not reproduce them.
Table 601 converts the construction type into hourly ratings for the structure: primary frame, bearing walls, nonbearing walls, floors and roofs. Table 602 rates exterior walls by how close they sit to the lot line (fire separation distance) and by occupancy group. Table 716.1(2) then tells you the rating the door assembly in each rated wall needs, which is usually lower than the wall itself.
Worked example. A Type IIA office needs a 1-hour primary structural frame under Table 601 — that is the spray fireproofing or board on every column and beam. Where the life-safety plan shows a 1-hour corridor fire partition, Table 716.1(2) calls for a 20-minute self-closing, latching door assembly in it.
Whether a corridor needs a rating at all is an egress question — see IBC egress requirements (Table 1020.2). Construction type also drives allowable height and area. This page is not a substitute for the design professional of record. Field PM keeps firestop photos, inspection sign-offs and RFIs on the job record so nothing gets covered up undocumented.
It lists the fire-resistance rating in hours that each building element — primary frame, bearing walls, nonbearing walls, floors and roofs — needs for each construction type. The construction type is set by the designer; Table 601 turns it into ratings. Read it free at codes.iccsafe.org.
Table 602 rates exterior walls based on their fire separation distance and the occupancy group — it protects neighbors from exposure. An exterior bearing wall must meet whichever of Table 601 or Table 602 is higher.
In a 1-hour fire partition corridor, Table 716.1(2) calls for a 20-minute door assembly that is self-closing and positive-latching. Other wall types (fire barriers, fire walls, shafts) require higher door ratings — check the table.
The distance measured at right angles from the face of the building to the nearest lot line, the centerline of a street, or an imaginary line between two buildings on the same lot. It drives both the exterior wall rating and how many openings are allowed.
The design professional of record. The contractor’s job is to build the listed assemblies exactly as specified, maintain labels and firestopping, and raise an RFI before substituting anything.