NEC 220.41 · 220.42 · 220.45 · 2023 NEC

How to calculate the NEC general lighting load

Unit load by occupancy, how the demand factors step down, where the 2023 NEC moved everything, and worked examples for a house and an office — with a free link to the official tables.

Need the actual tables? Look up Tables 220.42(A) and 220.45 in the free NFPA viewer →

Where the rules moved in the 2023 NEC

What it covers2020 NEC2023 NEC
Dwelling-unit minimum load per square footTable 220.12 (dwelling row) and 220.14(J)220.41
Unit lighting load for non-dwelling occupancies220.12 / Table 220.12220.42 / Table 220.42(A)
Lighting load demand factors220.42 / Table 220.42220.45 / Table 220.45
Non-dwelling receptacle demand220.44220.47
Floor-area rule (what square footage counts)Garages excludedGarages no longer excluded — only open porches and unfinished areas not adaptable for future use

Method is essentially unchanged — mostly a reorganization of Article 220. Older plan-review comments and textbooks will still cite the 2020 numbers. Our own summary of the 2023 NEC, not the code text. Look up Tables 220.42(A) and 220.45 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice — service sizing is the designer of record’s call.

How the general lighting load fits a service calculation

StepWhat you doWatch out for
1Measure the floor area from outside dimensionsLeave out open porches and unfinished areas not adaptable for future use. The 2023 NEC dropped the garage exclusion — garages now count (220.5(C))
2Pick the occupancy and read the VA per square foot (220.41 for dwellings, Table 220.42(A) otherwise)Use the occupancy that matches how the space is actually used, not the zoning label
3Multiply area × unit loadThis is a minimum — if the actual connected lighting is higher, use the higher number
4Dwellings: add the small-appliance and laundry circuits (220.52) to the lighting totalThey go in before the demand factors, not after
5Apply the Table 220.45 demand factors for the occupancyMany non-dwelling occupancies (offices, stores) get no lighting demand reduction
6Carry the result to the service or feeder calc; apply 125% to continuous load where 215.2 / 230.42 require itCommercial lighting is typically continuous (3 hours or more)

Our own summary of the 2023 NEC, not the code text. Look up Tables 220.42(A) and 220.45 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice — service sizing is the designer of record’s call.

Worked example 1 — 2,000 sq ft single-family dwelling

Input / stepValueSource
Floor area (incl. garage under 2023 rules)2,000 sq ftPlans, outside dimensions — 220.5(C)
General lighting & receptacles2,000 × 3 VA = 6,000 VA220.41
Two small-appliance circuits + one laundry circuit4,500 VA220.52
Total before demand10,500 VASum
First 3,000 VA at 100%3,000 VATable 220.45
Remaining 7,500 VA at 35%2,625 VATable 220.45
Net general lighting load5,625 VACarry to the Part III (standard method) service calc

Worked example values only. Larger dwellings reach a further demand step — look up the full table in the free NFPA viewer.

Worked example 2 — 5,000 sq ft office tenant space

Input / stepValueSource
Floor area5,000 sq ftPlans
Unit load, office1.3 VA per sq ftTable 220.42(A)
Lighting load6,500 VA5,000 × 1.3
Demand factorNone for offices — 100%Table 220.45
Continuous-load sizing6,500 × 125% = 8,125 VA215.2 / 230.42
Plus receptacles (60 × 180 VA = 10,800 VA)First 10 kVA at 100%, rest at 50% → 10,400 VA220.14(I), 220.47

Worked example values only. If the lighting design connects more than the unit load, use the actual connected load.

Common mistakes

MistakeWhat to do instead
Applying dwelling demand factors to an office or storeCheck the occupancy row in Table 220.45 — many commercial occupancies are taken at 100%
Adding small-appliance and laundry VA after the demand factorInclude them in the total that the Table 220.45 steps are applied to
Using the unit load when the actual lighting is higherThe table is a floor, not a ceiling
Forgetting 125% on continuous commercial lightingApply the continuous-load factor when sizing the feeder or service conductors and OCPD
Leaving the garage out of a 2023-code dwelling calcUnder the 2023 NEC the garage area counts toward the floor area
Citing 2020 section numbers on a 2023 jobUpdate submittals and calc sheets — the plan reviewer will flag it

Our own summary of the 2023 NEC, not the code text. Look up Tables 220.42(A) and 220.45 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice — service sizing is the designer of record’s call.

📋 Embed this chart on your site — freeGet the code →

Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.

<iframe src="https://www.field-pm.com/embed/charts/nec-general-lighting-load-calculation" title="General Lighting Load (NEC 220.42/220.45) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe>
<p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nec-general-lighting-load-calculation" target="_blank" rel="noopener">General Lighting Load (NEC 220.42/220.45)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>

The first line of every service calc

Look up Tables 220.42(A) and 220.45 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how the tables work; it does not reproduce them. Written to the 2023 NEC — verify against the edition your AHJ has adopted.

It starts with square feet. The general lighting load is a minimum volt-amperes-per-square-foot figure set by occupancy. For dwellings it lives in 220.41 and also covers the general-use receptacles; for everything else, Table 220.42(A) lists unit loads by occupancy type. Multiply the area by the unit load and you have the connected general lighting load — unless the actual lighting is higher, in which case the actual load governs.

Then the demand factors. Table 220.45 recognizes that not everything is on at once. Dwellings, hotels, hospitals, and warehouses step down in blocks — the first block at full value and later blocks at reduced percentages. Most other occupancies, including offices and stores, stay at 100%. In a dwelling, the small-appliance and laundry circuits are added to the lighting total before those steps are applied.

2023 renumbering. Article 220 was reorganized: the old Table 220.12 unit loads are now Table 220.42(A), the dwelling minimum is 220.41, and the demand factors that used to be Table 220.42 are now Table 220.45. If a textbook or old calc sheet says “220.42 demand factors,” it is a 2020-or-earlier reference.

After the lighting load, the calc moves on to appliances, HVAC, and motors — see the cooking appliance demand guide and, for apartment buildings, the multifamily optional method. Size the conductors with the NEC 310.16 ampacity chart, pick the OCPD from the standard breaker sizes guide, lay out circuits on the panel schedule template, and check long runs with the voltage drop calculator.

FAQ

What is the general lighting load for a house?+

Under the 2023 NEC, 220.41 sets a minimum of 3 VA per square foot for dwelling units, which also covers the general-use receptacles. Add the small-appliance and laundry circuits from 220.52, then apply the Table 220.45 demand factors. Look up the table in the free NFPA viewer at nfpa.org/freeaccess.

Where did Table 220.12 go in the 2023 NEC?+

The non-dwelling unit loads moved to Table 220.42(A), the dwelling minimum moved to 220.41, and the lighting demand factors that used to be Table 220.42 became Table 220.45. The method is essentially the same.

Do offices get a lighting demand factor?+

Not for general lighting — under Table 220.45, occupancies not specifically listed are taken at 100%. Office receptacle loads are handled separately under 220.47, where the portion above 10 kVA can be taken at 50%.

Is general lighting a continuous load?+

In commercial work it usually is, because it runs three hours or more. Feeder and service conductors and overcurrent devices are then sized at 125% of the continuous portion under 215.2, 215.3, and 230.42.

Can I use the energy code lighting power density instead?+

Article 220 includes a conditional allowance for using an adopted energy code’s lighting power density in some non-dwelling occupancies, with monitoring and other conditions. Check the exact wording and conditions in your adopted edition before relying on it.