NEC 430.22 · 430.52 · 430.32 · Motor circuits

How to size motor branch-circuit protection

Conductors at 125% of table FLC, the breaker or fuse by device type, the next-size-up exception, and overloads from the nameplate — with a worked example and a free link to the official tables.

Need the actual table? Look up Table 430.52(C)(1) in the free NFPA viewer →

Three pieces, three rules — which number comes from where

Piece of the circuitWhat it protects againstSized fromRule
Branch-circuit conductorsCarrying running current continuouslyTable FLC (430.248/430.250), not nameplate430.22 — 125% of FLC
Breaker or fuses (SC/GF device)Short circuits and ground faults onlyTable FLC × percentage for the device type430.52 + Table 430.52(C)(1)
Overload relay / heatersMotor running overloaded, failing to startNameplate FLA, adjusted by service factor / temp rise430.32
DisconnectIsolation for serviceHorsepower rating or table FLC430.109 / 430.110

Our own summary of the 2023 NEC, not the code text. Look up Article 430 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice.

How to read Table 430.52(C)(1), step by step

StepWhat you doWatch out for
1Get the motor FLC from Table 430.250 (3-phase) or 430.248 (1-phase) for the hp and voltageNameplate amps are for the overloads, not this step (430.6(A))
2Find the row for the motor type — most jobs are "other than wound-rotor" squirrel-cage motorsWound-rotor and DC motors have their own rows
3Pick the column for the device you are installing: nontime-delay fuse, dual-element (time-delay) fuse, instantaneous-trip breaker, or inverse-time breakerEach device type has a different percentage — they are not interchangeable
4Multiply FLC × that percentageThat result is a maximum, not a target
5If the result is not a standard size in 240.6(A), Exception No. 1 lets you go up to the next standard sizeGo up one standard size only
6If the motor still trips on start, Exception No. 2 allows a higher ceiling for each device typeOnly after the first size proves it will not carry the start — check your edition for the ceilings

Our own summary of the 2023 NEC, not the code text. Look up Article 430 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice.

Worked example — 7.5 hp, 460 V, 3-phase squirrel-cage motor, inverse-time breaker

Input / stepValueSource
Table FLC11 ATable 430.250, 460 V column
Conductor minimum ampacity11 × 1.25 = 13.75 A430.22
Conductor14 AWG Cu minimum (many shops run 12)Table 310.16, check terminal temp rating
Inverse-time breaker maximum11 × 2.50 = 27.5 ATable 430.52(C)(1)
Breaker size30 A (next standard size up)430.52(C)(1) Exc. 1 + 240.6(A)
Nameplate FLA (from the motor)10.5 A, SF 1.15Motor nameplate
Overload maximum10.5 × 1.25 = 13.1 A430.32(A)(1), SF ≥ 1.15

Worked example values only — the 250% and 125% factors shown are the two this example uses. Look up the full tables in the free NFPA viewer.

Common field mistakes

MistakeWhat to do instead
Sizing the breaker from nameplate FLAUse table FLC for conductors and SC/GF protection; nameplate is for overloads
Thinking a 30 A breaker on 14 AWG is a violationMotor SC/GF protection may exceed conductor ampacity because the overload protects the wire (240.4(G) points to Art. 430)
Skipping the overload because "the breaker covers it"The breaker is short-circuit/ground-fault only; overload protection is a separate requirement
Jumping straight to Exception No. 2 ceilingsStart at the table percentage; Exception No. 2 is only for a motor that will not start
Going up two standard sizesException No. 1 allows the next standard size up, one step
Using an instantaneous-trip breaker as a loose partInstantaneous-trip (MCP) breakers are only allowed as part of a listed combination controller

Our own summary of the 2023 NEC, not the code text. Look up Article 430 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice.

📋 Embed this chart on your site — freeGet the code →

Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.

<iframe src="https://www.field-pm.com/embed/charts/motor-branch-circuit-protection" title="Motor Branch-Circuit Protection (NEC 430.52) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe>
<p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/motor-branch-circuit-protection" target="_blank" rel="noopener">Motor Branch-Circuit Protection (NEC 430.52)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>

Why a motor circuit breaks the normal wire-and-breaker rules

Look up Article 430 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how to use Table 430.52(C)(1) and the related sections; it does not reproduce the table.

On a lighting or receptacle circuit, one breaker protects the wire from everything. A motor circuit splits that job. The branch-circuit short-circuit and ground-fault device (breaker or fuses) only has to clear faults, so it is sized big enough to ride through inrush. The overload relay protects the motor and the wire from running hot. And the conductors are sized at 125% of the table full-load current. Three numbers, three sections — and it is normal for the breaker to be larger than the wire’s ampacity.

Table FLC vs nameplate. 430.6(A) says to use the NEC table full-load current — not the nameplate — for conductors, the SC/GF device, and the disconnect. The nameplate FLA is only used for the overloads. Pull the table value from the motor full-load current chart guide.

Worked example. A 7.5 hp, 460 V three-phase motor has a table FLC of 11 A. Conductors: 11 × 125% = 13.75 A, so 14 AWG copper is the minimum. Inverse-time breaker: 11 × 250% = 27.5 A — not a standard size, so Exception No. 1 lets you go to 30 A (see the standard breaker sizes guide). With a nameplate of 10.5 A and a 1.15 service factor, the overload tops out at about 13.1 A. If the motor will not start on that breaker, Exception No. 2 allows a higher ceiling — check your edition.

For conductor ampacity and derating on long or crowded motor feeds, see the NEC 310.16 ampacity chart and the ampacity correction factors guide. For starting current, see motor locked-rotor code letters; for the starter itself, NEMA starter sizes. Field PM keeps motor schedules, submittals, and inspection records attached to the job.

FAQ

How do I size a breaker for a motor?+

Take the motor full-load current from NEC Table 430.250 (three-phase) or 430.248 (single-phase), multiply it by the percentage for your device type in Table 430.52(C)(1), and use that as the maximum. If the result is not a standard size, 430.52(C)(1) Exception No. 1 lets you use the next standard size up. For example, an inverse-time breaker for a motor with an 11 A table FLC works out to 27.5 A, so a 30 A breaker is allowed.

Why is the motor breaker bigger than the wire ampacity?+

The breaker on a motor circuit only has to clear short circuits and ground faults; it must be sized large enough to ride through locked-rotor starting current. The overload relay, sized to the nameplate, is what protects the conductors and motor from overload. Section 240.4(G) sends motor circuits to Article 430 for exactly this reason.

Do I size motor wire at 125%?+

Yes. Under 430.22, a single motor branch circuit needs conductors with an ampacity of at least 125% of the motor full-load current from the NEC tables (not the nameplate), then you pick the conductor from Table 310.16 with the correct terminal temperature column.

How do I size motor overloads?+

Under 430.32, overloads are sized from the nameplate full-load amps, with a percentage that depends on the service factor and marked temperature rise. A motor with a service factor of 1.15 or more gets the higher allowance; others get a lower one. Check the section in your edition for the exact values and the further allowance if the motor will not start.

Did the table number change in the 2023 NEC?+

Yes. The table formerly cited as Table 430.52 is referenced in the 2023 NEC as Table 430.52(C)(1), matching the subsection that uses it. The sizing method is the same. The 2023 edition also added 10 A as a standard fuse and inverse-time breaker size in 240.6(A).

Built by a contractor, for the field

Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.

Start free trial →

More reference charts

Rated by contractors on

Field PM reviews on CapterraField PM reviews on GetAppField PM reviews on Software Advice