NEC 430.22 · 430.52 · 430.32 · Motor circuits
Conductors at 125% of table FLC, the breaker or fuse by device type, the next-size-up exception, and overloads from the nameplate — with a worked example and a free link to the official tables.
Need the actual table? Look up Table 430.52(C)(1) in the free NFPA viewer →
| Piece of the circuit | What it protects against | Sized from | Rule |
|---|---|---|---|
| Branch-circuit conductors | Carrying running current continuously | Table FLC (430.248/430.250), not nameplate | 430.22 — 125% of FLC |
| Breaker or fuses (SC/GF device) | Short circuits and ground faults only | Table FLC × percentage for the device type | 430.52 + Table 430.52(C)(1) |
| Overload relay / heaters | Motor running overloaded, failing to start | Nameplate FLA, adjusted by service factor / temp rise | 430.32 |
| Disconnect | Isolation for service | Horsepower rating or table FLC | 430.109 / 430.110 |
Our own summary of the 2023 NEC, not the code text. Look up Article 430 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice.
| Step | What you do | Watch out for |
|---|---|---|
| 1 | Get the motor FLC from Table 430.250 (3-phase) or 430.248 (1-phase) for the hp and voltage | Nameplate amps are for the overloads, not this step (430.6(A)) |
| 2 | Find the row for the motor type — most jobs are "other than wound-rotor" squirrel-cage motors | Wound-rotor and DC motors have their own rows |
| 3 | Pick the column for the device you are installing: nontime-delay fuse, dual-element (time-delay) fuse, instantaneous-trip breaker, or inverse-time breaker | Each device type has a different percentage — they are not interchangeable |
| 4 | Multiply FLC × that percentage | That result is a maximum, not a target |
| 5 | If the result is not a standard size in 240.6(A), Exception No. 1 lets you go up to the next standard size | Go up one standard size only |
| 6 | If the motor still trips on start, Exception No. 2 allows a higher ceiling for each device type | Only after the first size proves it will not carry the start — check your edition for the ceilings |
Our own summary of the 2023 NEC, not the code text. Look up Article 430 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice.
| Input / step | Value | Source |
|---|---|---|
| Table FLC | 11 A | Table 430.250, 460 V column |
| Conductor minimum ampacity | 11 × 1.25 = 13.75 A | 430.22 |
| Conductor | 14 AWG Cu minimum (many shops run 12) | Table 310.16, check terminal temp rating |
| Inverse-time breaker maximum | 11 × 2.50 = 27.5 A | Table 430.52(C)(1) |
| Breaker size | 30 A (next standard size up) | 430.52(C)(1) Exc. 1 + 240.6(A) |
| Nameplate FLA (from the motor) | 10.5 A, SF 1.15 | Motor nameplate |
| Overload maximum | 10.5 × 1.25 = 13.1 A | 430.32(A)(1), SF ≥ 1.15 |
Worked example values only — the 250% and 125% factors shown are the two this example uses. Look up the full tables in the free NFPA viewer.
| Mistake | What to do instead |
|---|---|
| Sizing the breaker from nameplate FLA | Use table FLC for conductors and SC/GF protection; nameplate is for overloads |
| Thinking a 30 A breaker on 14 AWG is a violation | Motor SC/GF protection may exceed conductor ampacity because the overload protects the wire (240.4(G) points to Art. 430) |
| Skipping the overload because "the breaker covers it" | The breaker is short-circuit/ground-fault only; overload protection is a separate requirement |
| Jumping straight to Exception No. 2 ceilings | Start at the table percentage; Exception No. 2 is only for a motor that will not start |
| Going up two standard sizes | Exception No. 1 allows the next standard size up, one step |
| Using an instantaneous-trip breaker as a loose part | Instantaneous-trip (MCP) breakers are only allowed as part of a listed combination controller |
Our own summary of the 2023 NEC, not the code text. Look up Article 430 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/motor-branch-circuit-protection" title="Motor Branch-Circuit Protection (NEC 430.52) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/motor-branch-circuit-protection" target="_blank" rel="noopener">Motor Branch-Circuit Protection (NEC 430.52)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Look up Article 430 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how to use Table 430.52(C)(1) and the related sections; it does not reproduce the table.
On a lighting or receptacle circuit, one breaker protects the wire from everything. A motor circuit splits that job. The branch-circuit short-circuit and ground-fault device (breaker or fuses) only has to clear faults, so it is sized big enough to ride through inrush. The overload relay protects the motor and the wire from running hot. And the conductors are sized at 125% of the table full-load current. Three numbers, three sections — and it is normal for the breaker to be larger than the wire’s ampacity.
Table FLC vs nameplate. 430.6(A) says to use the NEC table full-load current — not the nameplate — for conductors, the SC/GF device, and the disconnect. The nameplate FLA is only used for the overloads. Pull the table value from the motor full-load current chart guide.
Worked example. A 7.5 hp, 460 V three-phase motor has a table FLC of 11 A. Conductors: 11 × 125% = 13.75 A, so 14 AWG copper is the minimum. Inverse-time breaker: 11 × 250% = 27.5 A — not a standard size, so Exception No. 1 lets you go to 30 A (see the standard breaker sizes guide). With a nameplate of 10.5 A and a 1.15 service factor, the overload tops out at about 13.1 A. If the motor will not start on that breaker, Exception No. 2 allows a higher ceiling — check your edition.
For conductor ampacity and derating on long or crowded motor feeds, see the NEC 310.16 ampacity chart and the ampacity correction factors guide. For starting current, see motor locked-rotor code letters; for the starter itself, NEMA starter sizes. Field PM keeps motor schedules, submittals, and inspection records attached to the job.
Take the motor full-load current from NEC Table 430.250 (three-phase) or 430.248 (single-phase), multiply it by the percentage for your device type in Table 430.52(C)(1), and use that as the maximum. If the result is not a standard size, 430.52(C)(1) Exception No. 1 lets you use the next standard size up. For example, an inverse-time breaker for a motor with an 11 A table FLC works out to 27.5 A, so a 30 A breaker is allowed.
The breaker on a motor circuit only has to clear short circuits and ground faults; it must be sized large enough to ride through locked-rotor starting current. The overload relay, sized to the nameplate, is what protects the conductors and motor from overload. Section 240.4(G) sends motor circuits to Article 430 for exactly this reason.
Yes. Under 430.22, a single motor branch circuit needs conductors with an ampacity of at least 125% of the motor full-load current from the NEC tables (not the nameplate), then you pick the conductor from Table 310.16 with the correct terminal temperature column.
Under 430.32, overloads are sized from the nameplate full-load amps, with a percentage that depends on the service factor and marked temperature rise. A motor with a service factor of 1.15 or more gets the higher allowance; others get a lower one. Check the section in your edition for the exact values and the further allowance if the motor will not start.
Yes. The table formerly cited as Table 430.52 is referenced in the 2023 NEC as Table 430.52(C)(1), matching the subsection that uses it. The sizing method is the same. The 2023 edition also added 10 A as a standard fuse and inverse-time breaker size in 240.6(A).
Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.
Start free trial →