NEC 310.12 · Dwelling services & feeders · 2023 NEC

How to use the NEC 310.12 83% rule for dwelling services

When residential service and main-feeder conductors can be sized at 83% of the rating, what it replaced, when derating kicks you off the shortcut table, and a worked 200 A example.

Need the actual text? Look up 310.12 and Table 310.12 in the free NFPA viewer →

Does the 83% rule apply to this conductor?

SituationUse 310.12?Why
Service to a one-family house, 120/240 V single-phaseYesCore case the rule was written for
Service to an individual unit in a two-family or multifamily buildingYesEach dwelling unit counts
Feeder that carries the whole load of the dwelling unit (e.g., meter-main to house panel)YesTreated like the service
Feeder to a subpanel, garage, or shop that carries only part of the loadNoSize from Table 310.16 and the calculated load
Service to a common-area / house panel in a multifamily buildingNoNot a dwelling unit
Dwelling fed from a 208Y/120 V system (two phases + neutral)Check your editionTreatment of services vs feeders differs — read the 208Y/120 text
Any case needing temperature correction or bundling adjustmentRule yes, shortcut table noApply the factors to the 310.16 ampacity

Our own summary of the 2023 NEC, not the code text. Look up 310.12 and Table 310.12 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

How to apply 310.12, step by step

StepWhat you doWatch out for
1Confirm the rule applies (dwelling unit, single-phase, whole-unit service or feeder, 100–400 A)Partial-load feeders are out
2Multiply the service or feeder rating by 0.83Use the rating (e.g., the main breaker), not the calculated load
3Pick a conductor whose Table 310.16 ampacity meets that number, in the column your terminations allowUsually 75 °C for service equipment
4If ambient correction or bundling applies, derate the 310.16 value and re-check it against the 83% targetThe shortcut Table 310.12 is only for no-derating installs
5Size the neutral from the calculated neutral load, but never below the grounding minimum220.61 and 250.24(C)(1)
6Size the GEC from the phase conductor you pickedTable 250.66

Our own summary of the 2023 NEC, not the code text. Look up 310.12 and Table 310.12 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

Worked example — 200 A single-family service, no derating

Input / stepValueSource
Service rating200 AMain breaker
Minimum conductor ampacity200 × 0.83 = 166 A310.12(A)
Copper choice, 75 °C column2/0 AWG Cu (175 A ≥ 166 A)Table 310.16
Aluminum choice, 75 °C column4/0 AWG Al (180 A ≥ 166 A)Table 310.16
Same run, but 40 °C attic with 90 °C wireDerate the 90 °C value, then compare to 166 A310.15(B)

Worked example values only. Look up the full tables in the free NFPA viewer.

Where the dwelling rule has lived

EditionLocationWhat it looked like
2014 and earlier310.15(B)(7) and Table 310.15(B)(7)A size-lookup table, with conditions
2017310.15(B)(7)Table removed; replaced with the 83% ampacity rule
2020310.12Moved to its own section; a shortcut table returned for no-derating installs
2023310.12Same approach: 83% rule, shortcut Table 310.12

Our own summary of the 2023 NEC, not the code text. Look up 310.12 and Table 310.12 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

Common field mistakes

MistakeWhat to do instead
Using the 83% rule for a subpanel feederOnly a feeder carrying the entire dwelling load qualifies
Reading Table 310.12 for conductors in a hot attic or bundled with othersOnce any correction or adjustment applies, go back to 310.16 and derate
Using an old Table 310.15(B)(7) cheat sheetCheck the 83% math against your adopted edition
Applying 83% to the calculated load instead of the ratingThe rule is based on the service or feeder rating
Assuming the rule covers commercial or three-phase servicesIt is limited to dwelling units
Reducing the neutral below the grounding minimumThe neutral still has to meet 250.24(C)(1) on a service

Our own summary of the 2023 NEC, not the code text. Look up 310.12 and Table 310.12 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

📋 Embed this chart on your site — freeGet the code →

Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.

<iframe src="https://www.field-pm.com/embed/charts/nec-dwelling-service-conductor-sizing" title="Dwelling Service 83% Rule (NEC 310.12) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe>
<p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nec-dwelling-service-conductor-sizing" target="_blank" rel="noopener">Dwelling Service 83% Rule (NEC 310.12)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>

The 83% rule in plain language

Look up 310.12 and Table 310.12 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how to use the rule; it does not reproduce the table.

A house almost never pulls its full service rating for long — the range, dryer, HVAC, and water heater don’t all peak together. The NEC recognizes that diversity in 310.12: for a single-family dwelling or an individual dwelling unit, the service conductors, and a feeder that carries the entire load of the unit, only need an ampacity of 83% of the service or feeder rating. It applies across the common residential range of service sizes (100–400 A in the 2023 text).

Worked example. A 200 A single-family service needs conductors rated at least 200 × 0.83 = 166 A. In the 75 °C column of Table 310.16, 2/0 copper (175 A) clears it, and so does 4/0 aluminum (180 A). Now run the same conductors through a hot attic: the shortcut table is off the table, so start from the 310.16 ampacity, apply the temperature correction factor, and check that the result still meets 166 A.

What it replaced. Older electricians learned the dwelling table at 310.15(B)(7) — a straight lookup of service rating to wire size. The 2017 NEC removed that table and replaced it with the 83% ampacity rule; the 2020 NEC moved the rule to 310.12 and added back a convenience table for installations with no correction or adjustment; the 2023 NEC kept that structure. Pocket charts printed before 2017 can steer you wrong, especially where derating applies.

Once the phase conductors are set, the GEC comes from the NEC 250.66 grounding electrode conductor guide, and the minimum service neutral from the Table 250.102(C)(1) guide. Check long service laterals with the voltage drop calculator. Heads-up for the next cycle: a later edition reportedly limits the rule to conductors rated 75 °C or higher, which matters for NM cable feeders — check when your state adopts it.

FAQ

What is the 83% rule?+

NEC 310.12 lets the service conductors — and a feeder that carries the whole load — for a single-family house or an individual dwelling unit have an ampacity of at least 83% of the service or feeder rating, instead of 100%. It exists because dwelling loads are diverse and rarely run near the full rating. Look up 310.12 in the free NFPA viewer at nfpa.org/freeaccess.

What size wire for a 200 amp residential service?+

Under the 83% rule, the conductors need at least 166 A of ampacity (200 × 0.83). With no derating and 75 °C terminations, that works out to 2/0 AWG copper or 4/0 AWG aluminum in Table 310.16. If the conductors need temperature correction or bundling adjustment, redo the math with the derated value.

What happened to Table 310.15(B)(7)?+

The 2017 NEC removed the old dwelling sizing table and replaced it with the 83% ampacity rule. The 2020 NEC moved the rule to 310.12 and brought back a shortcut table for installations with no correction or adjustment factors, and the 2023 NEC kept that approach.

Can I use the 83% rule for a subpanel?+

Only if the feeder carries the entire load of the dwelling unit, such as the feeder from an outdoor meter-main to the indoor panel. A feeder to a garage, shop, or partial-load subpanel is sized from the calculated load and Table 310.16.

Does the 83% rule apply to the neutral?+

The neutral is sized from the calculated unbalanced load, and on a service it can never be smaller than the minimum in 250.24(C)(1). For some 208Y/120 V dwelling feeders, the edition's text limits neutral reduction — read 310.12 in the edition your AHJ enforces.