NEC 310.12 · Dwelling services & feeders · 2023 NEC
When residential service and main-feeder conductors can be sized at 83% of the rating, what it replaced, when derating kicks you off the shortcut table, and a worked 200 A example.
Need the actual text? Look up 310.12 and Table 310.12 in the free NFPA viewer →
| Situation | Use 310.12? | Why |
|---|---|---|
| Service to a one-family house, 120/240 V single-phase | Yes | Core case the rule was written for |
| Service to an individual unit in a two-family or multifamily building | Yes | Each dwelling unit counts |
| Feeder that carries the whole load of the dwelling unit (e.g., meter-main to house panel) | Yes | Treated like the service |
| Feeder to a subpanel, garage, or shop that carries only part of the load | No | Size from Table 310.16 and the calculated load |
| Service to a common-area / house panel in a multifamily building | No | Not a dwelling unit |
| Dwelling fed from a 208Y/120 V system (two phases + neutral) | Check your edition | Treatment of services vs feeders differs — read the 208Y/120 text |
| Any case needing temperature correction or bundling adjustment | Rule yes, shortcut table no | Apply the factors to the 310.16 ampacity |
Our own summary of the 2023 NEC, not the code text. Look up 310.12 and Table 310.12 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
| Step | What you do | Watch out for |
|---|---|---|
| 1 | Confirm the rule applies (dwelling unit, single-phase, whole-unit service or feeder, 100–400 A) | Partial-load feeders are out |
| 2 | Multiply the service or feeder rating by 0.83 | Use the rating (e.g., the main breaker), not the calculated load |
| 3 | Pick a conductor whose Table 310.16 ampacity meets that number, in the column your terminations allow | Usually 75 °C for service equipment |
| 4 | If ambient correction or bundling applies, derate the 310.16 value and re-check it against the 83% target | The shortcut Table 310.12 is only for no-derating installs |
| 5 | Size the neutral from the calculated neutral load, but never below the grounding minimum | 220.61 and 250.24(C)(1) |
| 6 | Size the GEC from the phase conductor you picked | Table 250.66 |
Our own summary of the 2023 NEC, not the code text. Look up 310.12 and Table 310.12 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
| Input / step | Value | Source |
|---|---|---|
| Service rating | 200 A | Main breaker |
| Minimum conductor ampacity | 200 × 0.83 = 166 A | 310.12(A) |
| Copper choice, 75 °C column | 2/0 AWG Cu (175 A ≥ 166 A) | Table 310.16 |
| Aluminum choice, 75 °C column | 4/0 AWG Al (180 A ≥ 166 A) | Table 310.16 |
| Same run, but 40 °C attic with 90 °C wire | Derate the 90 °C value, then compare to 166 A | 310.15(B) |
Worked example values only. Look up the full tables in the free NFPA viewer.
| Edition | Location | What it looked like |
|---|---|---|
| 2014 and earlier | 310.15(B)(7) and Table 310.15(B)(7) | A size-lookup table, with conditions |
| 2017 | 310.15(B)(7) | Table removed; replaced with the 83% ampacity rule |
| 2020 | 310.12 | Moved to its own section; a shortcut table returned for no-derating installs |
| 2023 | 310.12 | Same approach: 83% rule, shortcut Table 310.12 |
Our own summary of the 2023 NEC, not the code text. Look up 310.12 and Table 310.12 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
| Mistake | What to do instead |
|---|---|
| Using the 83% rule for a subpanel feeder | Only a feeder carrying the entire dwelling load qualifies |
| Reading Table 310.12 for conductors in a hot attic or bundled with others | Once any correction or adjustment applies, go back to 310.16 and derate |
| Using an old Table 310.15(B)(7) cheat sheet | Check the 83% math against your adopted edition |
| Applying 83% to the calculated load instead of the rating | The rule is based on the service or feeder rating |
| Assuming the rule covers commercial or three-phase services | It is limited to dwelling units |
| Reducing the neutral below the grounding minimum | The neutral still has to meet 250.24(C)(1) on a service |
Our own summary of the 2023 NEC, not the code text. Look up 310.12 and Table 310.12 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/nec-dwelling-service-conductor-sizing" title="Dwelling Service 83% Rule (NEC 310.12) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nec-dwelling-service-conductor-sizing" target="_blank" rel="noopener">Dwelling Service 83% Rule (NEC 310.12)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Look up 310.12 and Table 310.12 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how to use the rule; it does not reproduce the table.
A house almost never pulls its full service rating for long — the range, dryer, HVAC, and water heater don’t all peak together. The NEC recognizes that diversity in 310.12: for a single-family dwelling or an individual dwelling unit, the service conductors, and a feeder that carries the entire load of the unit, only need an ampacity of 83% of the service or feeder rating. It applies across the common residential range of service sizes (100–400 A in the 2023 text).
Worked example. A 200 A single-family service needs conductors rated at least 200 × 0.83 = 166 A. In the 75 °C column of Table 310.16, 2/0 copper (175 A) clears it, and so does 4/0 aluminum (180 A). Now run the same conductors through a hot attic: the shortcut table is off the table, so start from the 310.16 ampacity, apply the temperature correction factor, and check that the result still meets 166 A.
What it replaced. Older electricians learned the dwelling table at 310.15(B)(7) — a straight lookup of service rating to wire size. The 2017 NEC removed that table and replaced it with the 83% ampacity rule; the 2020 NEC moved the rule to 310.12 and added back a convenience table for installations with no correction or adjustment; the 2023 NEC kept that structure. Pocket charts printed before 2017 can steer you wrong, especially where derating applies.
Once the phase conductors are set, the GEC comes from the NEC 250.66 grounding electrode conductor guide, and the minimum service neutral from the Table 250.102(C)(1) guide. Check long service laterals with the voltage drop calculator. Heads-up for the next cycle: a later edition reportedly limits the rule to conductors rated 75 °C or higher, which matters for NM cable feeders — check when your state adopts it.
NEC 310.12 lets the service conductors — and a feeder that carries the whole load — for a single-family house or an individual dwelling unit have an ampacity of at least 83% of the service or feeder rating, instead of 100%. It exists because dwelling loads are diverse and rarely run near the full rating. Look up 310.12 in the free NFPA viewer at nfpa.org/freeaccess.
Under the 83% rule, the conductors need at least 166 A of ampacity (200 × 0.83). With no derating and 75 °C terminations, that works out to 2/0 AWG copper or 4/0 AWG aluminum in Table 310.16. If the conductors need temperature correction or bundling adjustment, redo the math with the derated value.
The 2017 NEC removed the old dwelling sizing table and replaced it with the 83% ampacity rule. The 2020 NEC moved the rule to 310.12 and brought back a shortcut table for installations with no correction or adjustment factors, and the 2023 NEC kept that approach.
Only if the feeder carries the entire load of the dwelling unit, such as the feeder from an outdoor meter-main to the indoor panel. A feeder to a garage, shop, or partial-load subpanel is sized from the calculated load and Table 310.16.
The neutral is sized from the calculated unbalanced load, and on a service it can never be smaller than the minimum in 250.24(C)(1). For some 208Y/120 V dwelling feeders, the edition's text limits neutral reduction — read 310.12 in the edition your AHJ enforces.