NEC 250.66 · Grounding electrode conductor
Which conductor you size from, how parallel sets work, the rod/Ufer/ground-ring limits, and why the GEC and EGC use different tables — with a free link to the official table.
Need the actual table? Look up Table 250.66 in the free NFPA viewer →
| Step | What you do | Watch out for |
|---|---|---|
| 1 | Identify the largest ungrounded (phase) service conductor — or the derived-system conductor for a transformer | Size from the phase conductors, not the main breaker and not the neutral |
| 2 | For parallel sets, add the circular-mil area of the conductors in one phase | Use the total of one phase, not the total of all phases |
| 3 | Pick the conductor-material column (copper, or aluminum / copper-clad aluminum) that matches the service conductors | The table has separate columns for the service conductor material and the GEC material |
| 4 | Read across that row to the GEC size in the material you are installing | Copper and aluminum GECs differ in size for the same row |
| 5 | Check whether an electrode-type limit applies (250.66(A)–(C)) | A GEC that is the only connection to a rod, Ufer, or ring may be smaller than the table row |
Our own summary, not the code text. Look up Table 250.66 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
| What the conductor connects | Sized by | Rule |
|---|---|---|
| Service or derived system → building steel, water pipe, or the electrode system generally | Largest ungrounded conductor | Table 250.66 |
| Only to rod, pipe, or plate electrodes | Table 250.66, but capped at a small fixed size | 250.66(A) |
| Only to a concrete-encased electrode (Ufer) | Table 250.66, but capped at a small fixed size | 250.66(B) |
| Only to a ground ring | Table 250.66, but never larger than the ring conductor | 250.66(C) |
| Equipment enclosures back to the source, with the circuit | Rating of the OCPD ahead of it | Table 250.122 (EGC — different table) |
Our own summary, not the code text. Look up Table 250.66 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
| Input / step | Value | Source |
|---|---|---|
| Conductors per phase | 3 × 350 kcmil Cu | Design |
| Equivalent area of one phase | 1050 kcmil | 3 × 350 |
| GEC to water pipe and building steel | 2/0 AWG Cu | Table 250.66, copper columns |
| Jumper that only goes to the ground rods | 6 AWG Cu | 250.66(A) limit |
| Jumper that only goes to the Ufer | 4 AWG Cu | 250.66(B) limit |
Worked example values only. Look up the full table in the free NFPA viewer.
| Mistake | What to do instead |
|---|---|
| Sizing the GEC from the main breaker rating | Use the largest ungrounded service conductor — the OCPD rating is for the EGC (250.122) |
| Using Table 250.122 for the GEC (or 250.66 for the EGC) | GEC → 250.66 (earth connection). EGC → 250.122 (fault-clearing path) |
| Upsizing the rod jumper to match the full table row | A jumper that is the sole connection to rods can stop at the 250.66(A) limit |
| Applying the rod limit to a GEC that continues to other electrodes | The limits only apply to the portion that is the sole connection to that electrode type |
| Forgetting to total parallel sets | Add the kcmil of one phase before entering the table |
Our own summary, not the code text. Look up Table 250.66 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/grounding-electrode-conductor-chart" title="Sizing the GEC (NEC 250.66) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/grounding-electrode-conductor-chart" target="_blank" rel="noopener">Sizing the GEC (NEC 250.66)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Look up Table 250.66 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how to use the table; it does not reproduce it.
The grounding electrode conductor (GEC) ties the service — or a separately derived system like a transformer secondary — to the grounding electrode system: building steel, the metal water pipe, the Ufer in the footing, ground rods. Table 250.66 sizes it by the largest ungrounded conductor, with separate columns for copper and aluminum service conductors and for a copper or aluminum GEC. The table also has a top row — once the service is large enough, the GEC stops growing.
The electrode-type limits. Three electrode types get a smaller ceiling when the conductor is the only connection to them: rods, pipes, and plates (250.66(A)); concrete-encased electrodes (250.66(B)); and ground rings (250.66(C)), which never need a conductor larger than the ring itself. That’s why a large commercial service can still land a small jumper on its rods.
Worked example. An 800 A service runs three parallel sets of 350 kcmil copper. One phase totals 1050 kcmil, which falls in the Table 250.66 row that calls for a 2/0 copper GEC — that’s the conductor to the water pipe and building steel. The jumper that only goes to the rods can stop at 6 AWG copper (250.66(A)), and the one that only goes to the Ufer at 4 AWG copper (250.66(B)).
Don’t mix up the two grounding tables: the equipment grounding conductor follows the breaker size — see the equipment grounding conductor chart (NEC 250.122). To size the service conductors themselves, start with the NEC 310.16 ampacity chart and the standard breaker sizes guide. Field PM keeps grounding inspections, photos, and as-builts with the job, so the record is there when the inspector asks.
Find the largest ungrounded service conductor (totaling parallel sets for one phase), find that size in the matching material column of NEC Table 250.66, and read across to the GEC size. Then check whether 250.66(A), (B), or (C) lets a smaller conductor serve a rod, Ufer, or ground ring. Look up Table 250.66 in the free NFPA viewer at nfpa.org/freeaccess.
Under 250.66(A), the part of the GEC that is the only connection to a rod, pipe, or plate electrode never needs to be larger than 6 AWG copper, however large the service is.
Under 250.66(B), the part of the GEC that is the only connection to a concrete-encased electrode never needs to be larger than 4 AWG copper.
The grounding electrode conductor (Table 250.66) connects the service or separately derived system to earth and is sized by the service conductor size. The equipment grounding conductor (Table 250.122) runs with each circuit so faults trip the breaker, and is sized by the OCPD rating. They answer different questions, so they use different tables.
The table has kept the same number through the 2017, 2020, and 2023 editions, and its basic structure — sizing by the largest ungrounded conductor — is unchanged. Wording in the headings has been revised over time, so read the edition your AHJ enforces.
Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.
Start free trial →