NEC 240.6(A) · Overcurrent protection
What the standard-ratings table is for, how the 240.4(B) next-size-up rule uses it, and the mistakes that get feeders red-tagged — with a free link to the official table.
Need the actual list? Look up Table 240.6(A) in the free NFPA viewer →
| Step | What you do | Why it matters |
|---|---|---|
| 1 | Find the conductor ampacity after all correction and adjustment factors | The rule compares the device to the final, derated ampacity — not the raw table value |
| 2 | Check whether that ampacity is itself a standard rating in Table 240.6(A) | If it is, that is your maximum device size — no bump |
| 3 | If not, find the next standard rating above it in the table | This is the only size the next-size-up rule can point to |
| 4 | Confirm the 240.4(B) conditions (see below) | The bump is conditional, and it stops at 800 A |
| 5 | Apply any specific limits that override the general rule | Small-conductor limits (240.4(D)), motor, and other article rules take precedence |
Our own summary, not the code text. Look up Table 240.6(A) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
| Condition | In plain terms |
|---|---|
| Not a multi-outlet circuit for portable cord-and-plug loads | A general receptacle branch circuit does not get the bump |
| Ampacity does not already match a standard rating | If the ampacity lands on a standard size, use that size |
| Next standard size is 800 A or less | Above 800 A, 240.4(C) requires ampacity at least equal to the device rating |
Our own summary, not the code text. Look up Table 240.6(A) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
| Input / step | Value | Source |
|---|---|---|
| Conductor | 500 kcmil Cu, 75 °C terminations, no derating | Design |
| Ampacity | 380 A | Table 310.16, 75 °C column |
| Is 380 A a standard rating? | No | Table 240.6(A) |
| Next standard rating above 380 A | 400 A | Table 240.6(A) |
| 240.4(B) conditions met? (feeder, ≤800 A) | Yes | 240.4(B) |
| Result | 400 A breaker permitted |
Worked example values only. Look up the full tables in the free NFPA viewer.
| Mistake | What to do instead |
|---|---|
| Bumping to the next size on a device over 800 A | Above 800 A there is no bump — add conductors or upsize them |
| Using the raw (non-derated) table ampacity | Apply temperature and bundling factors first, then look for the next standard size |
| Bumping a small conductor past its 240.4(D) limit | The small-conductor limits cap 14–10 AWG regardless of the next-size-up rule |
| Assuming a size is standard because it is sold | Nonstandard ratings are allowed, but only listed ratings count for "next standard size" |
| Assuming the low end of the list is the same in every edition | Check your adopted edition — the 2023 NEC revised the low ratings and which are fuse-only |
Our own summary, not the code text. Look up Table 240.6(A) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/standard-breaker-sizes-chart" title="Standard OCPD Sizes (NEC 240.6) Explained — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/standard-breaker-sizes-chart" target="_blank" rel="noopener">Standard OCPD Sizes (NEC 240.6) Explained</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Look up Table 240.6(A) in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how to use the table; it does not reproduce it.
NEC 240.6(A) doesn’t tell you what breaker to install — it defines which ratings count as standard. That matters because several rules only let you step up to "the next higher standard rating." The most common is 240.4(B): when a conductor’s ampacity falls between standard sizes, you may use the next standard size up, as long as you’re at or below 800 A and it isn’t a multi-outlet circuit for portable loads.
Worked example. A feeder uses one set of 500 kcmil copper on 75 °C terminals with no derating. Per Table 310.16, that’s 380 A. 380 A isn’t a standard rating, and the next standard size in Table 240.6(A) is 400 A — so a 400 A breaker is permitted. Now suppose the same conductors are paralleled for a 1200 A service: three sets give 1140 A. That device is over 800 A, so 240.4(C) applies and 1140 A is not enough. You need a fourth set or larger conductors.
Before you pick the device, derate the conductors with the ampacity correction and adjustment factors guide, and respect the small-conductor limits covered in the wire size & breaker chart. After the device is chosen, the ground follows the breaker — see the equipment grounding conductor chart (NEC 250.122). Motor circuits have their own rules; start from the motor full-load current chart.
Edition note: the 2023 NEC revised the low end of the standard-ratings list and which small ratings are fuse-only — check the wording in the edition your AHJ enforces. Record final breaker sizes circuit by circuit on the panel schedule template; Field PM keeps panel schedules, inspections, and QA/QC together with the job.
It lists the ampere ratings that the Code treats as "standard" for fuses and inverse-time circuit breakers. Other ratings are allowed, but rules that say "the next higher standard rating" — like 240.4(B) and several motor-circuit rules — point to this list. Look up Table 240.6(A) in the free NFPA viewer at nfpa.org/freeaccess.
NEC 240.4(B) lets you protect a conductor with the next higher standard device rating when its ampacity does not match a standard rating, provided the circuit is not a multi-outlet branch circuit supplying cord-and-plug portable loads and the next size is 800 A or less. Example: 500 kcmil copper at 75 °C is 380 A per Table 310.16, so a 400 A device is permitted.
The bump goes away. Under 240.4(C), when the device is rated over 800 A, the conductor ampacity must be equal to or greater than the device rating. That usually means adding a parallel set or going to larger conductors.
Yes — the 2023 edition revised the low end of Table 240.6(A), including which small ratings apply to breakers versus fuses only. If your jurisdiction is on 2017 or 2020, check that edition's wording before relying on a low-amp rating.
Separately. 240.6(B) and (C) explain how to determine the rating of an adjustable-trip breaker — generally its maximum possible setting, unless access to the adjustment is restricted as the Code describes.
Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.
Start free trial →