NEC 310.17 · Free air ampacity · 2023 NEC
When single conductors get the higher free-air rating, how cable tray rules take a percentage of it, and a worked single-conductor tray example.
Need the actual tables? Look up Tables 310.16 and 310.17 in the free NFPA viewer →
| Installation | Starting table | Notes |
|---|---|---|
| Conductors in conduit, EMT, or other raceway | 310.16 | Most building wiring |
| Cable (MC, NM, SE, TC) or direct burial | 310.16 | Plus any cable-specific limits |
| Single insulated conductors in free air, spaced apart (open wiring on insulators, overhead spans) | 310.17 | Heat escapes freely — higher ampacity |
| Single conductors 1/0 and larger in uncovered cable tray | A percentage of 310.17 | 392.80(A)(2); size-dependent percentage |
| Single conductors in tray, single layer, spaced one diameter apart | 310.17 | 392.80(A)(2) — full free-air value |
| Single conductors bundled in triangular or square configuration in tray | Free-air tables for triplexed or quadruplexed conductors (310.20) | 392.80(A)(2); spacing rules apply |
| Multiconductor cable in tray | 310.16, with tray adjustments | 392.80(A)(1) — different rules |
Our own summary of the 2023 NEC, not the code text. Look up Tables 310.16 and 310.17 and 392.80 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
| Step | What you do | Watch out for |
|---|---|---|
| 1 | Confirm the conductors are single conductors actually in free air (or a tray condition that sends you to 310.17) | A conduit sleeve or covered tray changes the answer |
| 2 | Pick the material and insulation-temperature column | Same 60/75/90 °C logic as 310.16 |
| 3 | Apply ambient temperature correction (the table assumes 30 °C) | Rooftop and outdoor runs often run hotter |
| 4 | For tray, apply the 392.80 percentage for the conductor size and configuration | Covered trays take a further reduction |
| 5 | Cap the result at the termination temperature ampacity (110.14(C)) | Terminations are rated using the 310.16 values, not free air |
| 6 | Check the OCPD and voltage drop | A higher ampacity doesn't fix a long run |
Our own summary of the 2023 NEC, not the code text. Look up Tables 310.16 and 310.17 and 392.80 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
| Input / step | Value | Source |
|---|---|---|
| Same conductor in conduit, 75 °C | 380 A | Table 310.16 |
| Free-air ampacity, 75 °C | 620 A | Table 310.17 |
| Tray rule for 1/0 through 500 kcmil singles | 65% of the 310.17 value | 392.80(A)(2) |
| Allowable ampacity in the tray | 0.65 × 620 = 403 A | Calculation |
| Same singles, single layer, spaced one diameter | Up to the full free-air value | 392.80(A)(2) |
Worked example values only. Look up the full tables in the free NFPA viewer. Termination and equipment ratings still control what you can actually connect.
| Mistake | What to do instead |
|---|---|
| Using 310.17 for a multiconductor cable (TC, MC) in tray | Multiconductor cable in tray follows 392.80(A)(1), based on 310.16 |
| Taking the full free-air value for singles touching each other in tray | Apply the 392.80 percentage unless the spacing rule is met |
| Forgetting the reduction when the tray gets a solid cover | Covered runs lose part of the free-air benefit — read 392.80 |
| Landing a free-air-sized conductor on 75 °C lugs without checking | Terminations are limited by 110.14(C) |
| Using free air for conductors that pass through a long enclosed sleeve or conduit | Enclosed sections can control — check the length and the 310.15 rules |
Our own summary of the 2023 NEC, not the code text. Look up Tables 310.16 and 310.17 and 392.80 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/nec-free-air-ampacity" title="Free Air Ampacity (NEC 310.17) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nec-free-air-ampacity" target="_blank" rel="noopener">Free Air Ampacity (NEC 310.17)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Look up Tables 310.16 and 310.17 and section 392.80 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how to use the tables; it does not reproduce them.
Ampacity is really a heat limit. A conductor in conduit is wrapped in air that can’t move and sits next to other warm conductors, so Table 310.16 is conservative. A single insulated conductor in free air sheds heat in every direction, so Table 310.17 gives it a much higher rating. Both tables assume a 30 °C ambient and use the same 60/75/90 °C columns.
Where contractors actually use it: cable tray. Section 392.80(A)(2) sizes single conductors 1/0 and larger in uncovered tray as a percentage of the 310.17 value — one percentage for 1/0 through 500 kcmil, a higher one for 600 kcmil and up — because conductors lying together in a tray are somewhere between free air and a conduit. If they’re laid in a single layer with a maintained space of one diameter, they can take the full free-air value; triplexed or triangular bundles use the configuration tables at 310.20. Multiconductor tray cable is a different animal and starts from 310.16.
Worked example. 500 kcmil copper at 75 °C is 380 A in conduit. As a single conductor in free air it’s 620 A. Laid in an uncovered ladder tray, 392.80(A)(2) allows 65% of the free-air value: 0.65 × 620 = 403 A — more than the conduit rating, which is why large feeders often go in tray. Then apply any ambient temperature correction and confirm the terminations and OCPD.
For tray runs, keep the grounding straight too: see the equipment grounding conductor guide (NEC 250.122). Not engineering advice — tray ampacity has several configuration-specific rules, so read 392.80 in the edition your AHJ enforces.
Table 310.16 covers conductors in a raceway, cable, or directly buried (not more than three current-carrying). Table 310.17 covers single insulated conductors in free air, which run cooler and so carry noticeably more current. Both assume a 30 °C ambient. Look them up in the free NFPA viewer at nfpa.org/freeaccess.
When single conductors are actually in free air, like open wiring on insulators, or when a cable tray rule in 392.80 sends you to 310.17 — usually as a percentage of the free-air value. Conductors in conduit or multiconductor cables use Table 310.16.
Under 392.80(A)(2), single conductors 1/0 and larger in uncovered tray get a percentage of the Table 310.17 value, with a different percentage for 1/0–500 kcmil and for 600 kcmil and up. For example, 500 kcmil copper at 75 °C is 620 A in free air; 65% of that is 403 A. Spaced single-layer and triangular configurations have their own rules.
Not automatically. Section 110.14(C) limits the conductor to the temperature rating of the terminations, and those limits are based on the 310.16 values. Large single conductors in tray often use 75 °C lugs — check the equipment.
Yes. Table 310.17 assumes a 30 °C ambient just like 310.16. If the conductors run hotter, apply the correction factors in 310.15(B).
Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.
Start free trial →