NEC 310.17 · Free air ampacity · 2023 NEC

How to use NEC Table 310.17 free air ampacity vs 310.16

When single conductors get the higher free-air rating, how cable tray rules take a percentage of it, and a worked single-conductor tray example.

Need the actual tables? Look up Tables 310.16 and 310.17 in the free NFPA viewer →

310.16 or 310.17? Which applies when

InstallationStarting tableNotes
Conductors in conduit, EMT, or other raceway310.16Most building wiring
Cable (MC, NM, SE, TC) or direct burial310.16Plus any cable-specific limits
Single insulated conductors in free air, spaced apart (open wiring on insulators, overhead spans)310.17Heat escapes freely — higher ampacity
Single conductors 1/0 and larger in uncovered cable trayA percentage of 310.17392.80(A)(2); size-dependent percentage
Single conductors in tray, single layer, spaced one diameter apart310.17392.80(A)(2) — full free-air value
Single conductors bundled in triangular or square configuration in trayFree-air tables for triplexed or quadruplexed conductors (310.20)392.80(A)(2); spacing rules apply
Multiconductor cable in tray310.16, with tray adjustments392.80(A)(1) — different rules

Our own summary of the 2023 NEC, not the code text. Look up Tables 310.16 and 310.17 and 392.80 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

How to use Table 310.17, step by step

StepWhat you doWatch out for
1Confirm the conductors are single conductors actually in free air (or a tray condition that sends you to 310.17)A conduit sleeve or covered tray changes the answer
2Pick the material and insulation-temperature columnSame 60/75/90 °C logic as 310.16
3Apply ambient temperature correction (the table assumes 30 °C)Rooftop and outdoor runs often run hotter
4For tray, apply the 392.80 percentage for the conductor size and configurationCovered trays take a further reduction
5Cap the result at the termination temperature ampacity (110.14(C))Terminations are rated using the 310.16 values, not free air
6Check the OCPD and voltage dropA higher ampacity doesn't fix a long run

Our own summary of the 2023 NEC, not the code text. Look up Tables 310.16 and 310.17 and 392.80 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

Worked example — 500 kcmil Cu single conductors (75 °C) in uncovered ladder tray

Input / stepValueSource
Same conductor in conduit, 75 °C380 ATable 310.16
Free-air ampacity, 75 °C620 ATable 310.17
Tray rule for 1/0 through 500 kcmil singles65% of the 310.17 value392.80(A)(2)
Allowable ampacity in the tray0.65 × 620 = 403 ACalculation
Same singles, single layer, spaced one diameterUp to the full free-air value392.80(A)(2)

Worked example values only. Look up the full tables in the free NFPA viewer. Termination and equipment ratings still control what you can actually connect.

Common field mistakes

MistakeWhat to do instead
Using 310.17 for a multiconductor cable (TC, MC) in trayMulticonductor cable in tray follows 392.80(A)(1), based on 310.16
Taking the full free-air value for singles touching each other in trayApply the 392.80 percentage unless the spacing rule is met
Forgetting the reduction when the tray gets a solid coverCovered runs lose part of the free-air benefit — read 392.80
Landing a free-air-sized conductor on 75 °C lugs without checkingTerminations are limited by 110.14(C)
Using free air for conductors that pass through a long enclosed sleeve or conduitEnclosed sections can control — check the length and the 310.15 rules

Our own summary of the 2023 NEC, not the code text. Look up Tables 310.16 and 310.17 and 392.80 in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

📋 Embed this chart on your site — freeGet the code →

Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.

<iframe src="https://www.field-pm.com/embed/charts/nec-free-air-ampacity" title="Free Air Ampacity (NEC 310.17) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe>
<p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nec-free-air-ampacity" target="_blank" rel="noopener">Free Air Ampacity (NEC 310.17)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>

Free air vs raceway, in plain language

Look up Tables 310.16 and 310.17 and section 392.80 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how to use the tables; it does not reproduce them.

Ampacity is really a heat limit. A conductor in conduit is wrapped in air that can’t move and sits next to other warm conductors, so Table 310.16 is conservative. A single insulated conductor in free air sheds heat in every direction, so Table 310.17 gives it a much higher rating. Both tables assume a 30 °C ambient and use the same 60/75/90 °C columns.

Where contractors actually use it: cable tray. Section 392.80(A)(2) sizes single conductors 1/0 and larger in uncovered tray as a percentage of the 310.17 value — one percentage for 1/0 through 500 kcmil, a higher one for 600 kcmil and up — because conductors lying together in a tray are somewhere between free air and a conduit. If they’re laid in a single layer with a maintained space of one diameter, they can take the full free-air value; triplexed or triangular bundles use the configuration tables at 310.20. Multiconductor tray cable is a different animal and starts from 310.16.

Worked example. 500 kcmil copper at 75 °C is 380 A in conduit. As a single conductor in free air it’s 620 A. Laid in an uncovered ladder tray, 392.80(A)(2) allows 65% of the free-air value: 0.65 × 620 = 403 A — more than the conduit rating, which is why large feeders often go in tray. Then apply any ambient temperature correction and confirm the terminations and OCPD.

For tray runs, keep the grounding straight too: see the equipment grounding conductor guide (NEC 250.122). Not engineering advice — tray ampacity has several configuration-specific rules, so read 392.80 in the edition your AHJ enforces.

FAQ

What is the difference between Table 310.16 and 310.17?+

Table 310.16 covers conductors in a raceway, cable, or directly buried (not more than three current-carrying). Table 310.17 covers single insulated conductors in free air, which run cooler and so carry noticeably more current. Both assume a 30 °C ambient. Look them up in the free NFPA viewer at nfpa.org/freeaccess.

When can I use free-air ampacity?+

When single conductors are actually in free air, like open wiring on insulators, or when a cable tray rule in 392.80 sends you to 310.17 — usually as a percentage of the free-air value. Conductors in conduit or multiconductor cables use Table 310.16.

How do I size single conductors in cable tray?+

Under 392.80(A)(2), single conductors 1/0 and larger in uncovered tray get a percentage of the Table 310.17 value, with a different percentage for 1/0–500 kcmil and for 600 kcmil and up. For example, 500 kcmil copper at 75 °C is 620 A in free air; 65% of that is 403 A. Spaced single-layer and triangular configurations have their own rules.

Can I terminate at the free-air ampacity?+

Not automatically. Section 110.14(C) limits the conductor to the temperature rating of the terminations, and those limits are based on the 310.16 values. Large single conductors in tray often use 75 °C lugs — check the equipment.

Does free air ampacity need temperature correction?+

Yes. Table 310.17 assumes a 30 °C ambient just like 310.16. If the conductors run hotter, apply the correction factors in 310.15(B).

Built by a contractor, for the field

Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.

Start free trial →

More reference charts

Rated by contractors on

Field PM reviews on CapterraField PM reviews on GetAppField PM reviews on Software Advice