NEC 450.3(A) · 450.3(B) · Transformers
Primary-only vs primary-and-secondary protection, next-size-up rules, impedance-based limits over 1000 V, and a worked 75 kVA 480-208Y/120 V example — with a free link to the official tables.
Need the actual tables? Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer →
| Situation | Table | What sets the limit |
|---|---|---|
| Transformer rated 1000 V or less (typical 480-208Y/120 V dry-type) | Table 450.3(B) | Protection scheme (primary only, or primary + secondary) and primary current range |
| Transformer rated over 1000 V (e.g. 12.47 kV-480 V pad-mount) | Table 450.3(A) | Transformer impedance, device type (breaker vs fuse), and location |
| Over 1000 V in a supervised location | Table 450.3(A), supervised rows | Qualified persons monitor and service the installation, so different limits apply |
| Conductors on either side of the transformer | Art. 240 (240.4, 240.21(C)) | Conductor ampacity — the 450.3 device does not automatically protect the wire |
Our own summary of the 2023 NEC, not the code text. Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice — medium-voltage protection should be designed and coordinated by an engineer.
| Step | What you do | Watch out for |
|---|---|---|
| 1 | Compute primary and secondary rated current from kVA: 3-phase I = kVA × 1000 ÷ (1.732 × V); 1-phase I = kVA × 1000 ÷ V | Use the transformer’s rated voltages, not the panel nominal |
| 2 | Choose the scheme: primary only, or primary with a secondary device | Primary-only is only an option if the secondary conductors are otherwise protected per 240.21(C) |
| 3 | Find the row for the primary current range | Small transformers (low primary current) have different percentages |
| 4 | Multiply rated current × the percentage for your scheme and side | These are maximums — smaller is always allowed |
| 5 | Apply Note 1: where the 125% value is not a standard size, the next standard size up is allowed | Note 1 does not apply to the higher primary ceiling in the primary + secondary scheme — round down there |
| 6 | Separately confirm every conductor is protected per Art. 240 | The most common inspection failure is a secondary conductor that is not protected at its ampacity |
Our own summary of the 2023 NEC, not the code text. Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice — medium-voltage protection should be designed and coordinated by an engineer.
| Input / step | Value | Source |
|---|---|---|
| Primary rated current | 75,000 ÷ (1.732 × 480) ≈ 90.2 A | Physics |
| Secondary rated current | 75,000 ÷ (1.732 × 208) ≈ 208.2 A | Physics |
| Primary only: max device | 90.2 × 125% ≈ 112.8 A → 125 A | Table 450.3(B) + Note 1 |
| Primary + secondary: secondary device | 208.2 × 125% ≈ 260 A → 300 A | Table 450.3(B) + Note 1 |
| Primary + secondary: primary ceiling | 90.2 × 250% ≈ 225.5 A → 225 A (round down) | Table 450.3(B) |
| Then check conductors | Secondary conductors protected per 240.21(C); primary feeder per 240.4 | Art. 240 |
Worked example values only — the 125% and 250% factors are the two this scheme uses. Look up the full table in the free NFPA viewer.
| Mistake | What to do instead |
|---|---|
| Sizing the primary breaker at the 250% ceiling with no secondary main | The higher primary limit only applies when a secondary device is also installed |
| Treating 450.3 compliance as conductor compliance | Check 240.21(C) tap rules and 240.4 for the conductors separately |
| Rounding up the 250% value | Next-size-up (Note 1) applies to the 125% cells; the higher primary ceiling is a hard cap |
| Setting the primary breaker too close to FLA | Transformer inrush can trip a tight breaker on energizing — pick a breaker with suitable trip characteristics |
| Using Table 450.3(B) on a medium-voltage unit | Over 1000 V uses Table 450.3(A), driven by impedance and location |
Our own summary of the 2023 NEC, not the code text. Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice — medium-voltage protection should be designed and coordinated by an engineer.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/transformer-overcurrent-protection" title="Transformer Overcurrent Protection (450.3) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/transformer-overcurrent-protection" target="_blank" rel="noopener">Transformer Overcurrent Protection (450.3)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer. This page explains how to apply them; it does not reproduce the tables.
Section 450.3 protects the transformer. For units rated 1000 V or less, Table 450.3(B) gives you two schemes: protect the primary only, with a tight limit, or protect both sides, which lets the primary device be much larger because the secondary device is doing the overload work. Over 1000 V, Table 450.3(A) bases the limits on the transformer’s nameplate impedance, the device type, and whether the location is supervised by qualified persons.
Worked example. A 75 kVA, 480-208Y/120 V dry-type draws about 90.2 A on the primary and 208 A on the secondary (kVA × 1000 ÷ 1.732 ÷ volts). Primary-only protection at 125% gives 112.8 A, and Note 1 lets you use 125 A. If you add a secondary main at 125% (260 A, next size up 300 A), the primary may go as high as 250% — 225.5 A, rounded down to 225 A. Standard sizes are covered in the standard breaker sizes guide.
Then protect the conductors. Passing 450.3 does not clear the wire. Secondary conductors need a 240.21(C) path — the 10 ft or 25 ft rules, or a secondary main at the transformer — and the primary feeder must be protected at its ampacity. Size those with the NEC 310.16 ampacity chart, and ground the derived system with the grounding electrode conductor guide.
Field PM keeps one-lines, transformer submittals, and inspection records together on the job, so the breaker in the panel matches the one on the drawing.
Compute the primary rated current from kVA and voltage, then apply the percentage from NEC Table 450.3(B) for your scheme. For a transformer 1000 V or less with primary-only protection and a primary current of 9 A or more, the limit is 125%, with the next standard size up permitted. For a 75 kVA, 480 V three-phase transformer (about 90.2 A), that allows a 125 A primary breaker. Look up the table in the free NFPA viewer at nfpa.org/freeaccess.
When the transformer also has secondary protection sized per Table 450.3(B), the primary device can go up to 250% of primary rated current. In that scheme you do not round the primary up to the next size. The conductors must still be protected per Article 240.
For three-phase: amps = kVA × 1000 ÷ (1.732 × line-to-line volts). For single-phase: amps = kVA × 1000 ÷ volts. A 75 kVA transformer is about 90.2 A at 480 V and about 208 A at 208 V.
Table 450.3(A) sets limits based on the transformer impedance, whether the device is a breaker or fuse, and whether the location is supervised by qualified persons. It is typically applied by an engineer as part of a coordination study, so we do not reproduce its values here — look them up in the free NFPA viewer.
Not automatically. Except in limited cases (such as a two-wire single-voltage secondary or a three-phase delta-delta, three-wire system under 240.4(F)), the secondary conductors need their own protection or must qualify under a 240.21(C) secondary-conductor rule.
Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.
Start free trial →