NEC 450.3(A) · 450.3(B) · Transformers

How to size transformer overcurrent protection

Primary-only vs primary-and-secondary protection, next-size-up rules, impedance-based limits over 1000 V, and a worked 75 kVA 480-208Y/120 V example — with a free link to the official tables.

Need the actual tables? Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer →

Which table and which column?

SituationTableWhat sets the limit
Transformer rated 1000 V or less (typical 480-208Y/120 V dry-type)Table 450.3(B)Protection scheme (primary only, or primary + secondary) and primary current range
Transformer rated over 1000 V (e.g. 12.47 kV-480 V pad-mount)Table 450.3(A)Transformer impedance, device type (breaker vs fuse), and location
Over 1000 V in a supervised locationTable 450.3(A), supervised rowsQualified persons monitor and service the installation, so different limits apply
Conductors on either side of the transformerArt. 240 (240.4, 240.21(C))Conductor ampacity — the 450.3 device does not automatically protect the wire

Our own summary of the 2023 NEC, not the code text. Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice — medium-voltage protection should be designed and coordinated by an engineer.

How to read Table 450.3(B), step by step

StepWhat you doWatch out for
1Compute primary and secondary rated current from kVA: 3-phase I = kVA × 1000 ÷ (1.732 × V); 1-phase I = kVA × 1000 ÷ VUse the transformer’s rated voltages, not the panel nominal
2Choose the scheme: primary only, or primary with a secondary devicePrimary-only is only an option if the secondary conductors are otherwise protected per 240.21(C)
3Find the row for the primary current rangeSmall transformers (low primary current) have different percentages
4Multiply rated current × the percentage for your scheme and sideThese are maximums — smaller is always allowed
5Apply Note 1: where the 125% value is not a standard size, the next standard size up is allowedNote 1 does not apply to the higher primary ceiling in the primary + secondary scheme — round down there
6Separately confirm every conductor is protected per Art. 240The most common inspection failure is a secondary conductor that is not protected at its ampacity

Our own summary of the 2023 NEC, not the code text. Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice — medium-voltage protection should be designed and coordinated by an engineer.

Worked example — 75 kVA, 480 V delta to 208Y/120 V, dry-type

Input / stepValueSource
Primary rated current75,000 ÷ (1.732 × 480) ≈ 90.2 APhysics
Secondary rated current75,000 ÷ (1.732 × 208) ≈ 208.2 APhysics
Primary only: max device90.2 × 125% ≈ 112.8 A → 125 ATable 450.3(B) + Note 1
Primary + secondary: secondary device208.2 × 125% ≈ 260 A → 300 ATable 450.3(B) + Note 1
Primary + secondary: primary ceiling90.2 × 250% ≈ 225.5 A → 225 A (round down)Table 450.3(B)
Then check conductorsSecondary conductors protected per 240.21(C); primary feeder per 240.4Art. 240

Worked example values only — the 125% and 250% factors are the two this scheme uses. Look up the full table in the free NFPA viewer.

Common field mistakes

MistakeWhat to do instead
Sizing the primary breaker at the 250% ceiling with no secondary mainThe higher primary limit only applies when a secondary device is also installed
Treating 450.3 compliance as conductor complianceCheck 240.21(C) tap rules and 240.4 for the conductors separately
Rounding up the 250% valueNext-size-up (Note 1) applies to the 125% cells; the higher primary ceiling is a hard cap
Setting the primary breaker too close to FLATransformer inrush can trip a tight breaker on energizing — pick a breaker with suitable trip characteristics
Using Table 450.3(B) on a medium-voltage unitOver 1000 V uses Table 450.3(A), driven by impedance and location

Our own summary of the 2023 NEC, not the code text. Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the edition adopted by your AHJ. Not engineering advice — medium-voltage protection should be designed and coordinated by an engineer.

📋 Embed this chart on your site — freeGet the code →

Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.

<iframe src="https://www.field-pm.com/embed/charts/transformer-overcurrent-protection" title="Transformer Overcurrent Protection (450.3) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe>
<p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/transformer-overcurrent-protection" target="_blank" rel="noopener">Transformer Overcurrent Protection (450.3)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>

Protecting the transformer vs protecting the wire

Look up Tables 450.3(A) and 450.3(B) in the free NFPA viewer. This page explains how to apply them; it does not reproduce the tables.

Section 450.3 protects the transformer. For units rated 1000 V or less, Table 450.3(B) gives you two schemes: protect the primary only, with a tight limit, or protect both sides, which lets the primary device be much larger because the secondary device is doing the overload work. Over 1000 V, Table 450.3(A) bases the limits on the transformer’s nameplate impedance, the device type, and whether the location is supervised by qualified persons.

Worked example. A 75 kVA, 480-208Y/120 V dry-type draws about 90.2 A on the primary and 208 A on the secondary (kVA × 1000 ÷ 1.732 ÷ volts). Primary-only protection at 125% gives 112.8 A, and Note 1 lets you use 125 A. If you add a secondary main at 125% (260 A, next size up 300 A), the primary may go as high as 250% — 225.5 A, rounded down to 225 A. Standard sizes are covered in the standard breaker sizes guide.

Then protect the conductors. Passing 450.3 does not clear the wire. Secondary conductors need a 240.21(C) path — the 10 ft or 25 ft rules, or a secondary main at the transformer — and the primary feeder must be protected at its ampacity. Size those with the NEC 310.16 ampacity chart, and ground the derived system with the grounding electrode conductor guide.

Field PM keeps one-lines, transformer submittals, and inspection records together on the job, so the breaker in the panel matches the one on the drawing.

FAQ

How do I size a transformer primary breaker?+

Compute the primary rated current from kVA and voltage, then apply the percentage from NEC Table 450.3(B) for your scheme. For a transformer 1000 V or less with primary-only protection and a primary current of 9 A or more, the limit is 125%, with the next standard size up permitted. For a 75 kVA, 480 V three-phase transformer (about 90.2 A), that allows a 125 A primary breaker. Look up the table in the free NFPA viewer at nfpa.org/freeaccess.

When can the primary breaker be larger?+

When the transformer also has secondary protection sized per Table 450.3(B), the primary device can go up to 250% of primary rated current. In that scheme you do not round the primary up to the next size. The conductors must still be protected per Article 240.

How do I calculate transformer full-load amps?+

For three-phase: amps = kVA × 1000 ÷ (1.732 × line-to-line volts). For single-phase: amps = kVA × 1000 ÷ volts. A 75 kVA transformer is about 90.2 A at 480 V and about 208 A at 208 V.

What is different about transformers over 1000 volts?+

Table 450.3(A) sets limits based on the transformer impedance, whether the device is a breaker or fuse, and whether the location is supervised by qualified persons. It is typically applied by an engineer as part of a coordination study, so we do not reproduce its values here — look them up in the free NFPA viewer.

Does the transformer breaker protect the secondary conductors?+

Not automatically. Except in limited cases (such as a two-wire single-voltage secondary or a three-phase delta-delta, three-wire system under 240.4(F)), the secondary conductors need their own protection or must qualify under a 240.21(C) secondary-conductor rule.

Built by a contractor, for the field

Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.

Start free trial →

More reference charts

Rated by contractors on

Field PM reviews on CapterraField PM reviews on GetAppField PM reviews on Software Advice