NEC 220.55 · 220.56 · 2023 NEC

How to use NEC Table 220.55 & 220.56 cooking appliance demand

Which column a range, cooktop, or oven falls into, how the notes adjust big ranges and combined circuits, and how commercial kitchen demand works — with worked examples and a free link to the official tables.

Need the actual tables? Look up Tables 220.55 and 220.56 in the free NFPA viewer →

How to read Table 220.55 (household cooking), step by step

StepWhat you doWatch out for
1List each household cooking appliance rated over 1¾ kW with its nameplate kWRanges, cooktops, wall ovens — count each appliance, not each burner
2Sort them by size: the smallest appliances fall under Column A, mid-size under Column B, and larger ones up to 12 kW under Column CColumns A and B are percentages of nameplate; Column C is a fixed kW value
3Find the row for the number of appliances in that groupThe row is the count, not the kW
4Ranges over 12 kW: raise the Column C value by the Note 1 percentage for every kW above 12Only whole kW above 12 count; the rule stops at 27 kW
5Unequal ranges over 8¾ kW: use Note 2 — average them, treating any under 12 kW as 12 kWThen apply Note 1 to the average
6Mixed groups: Note 3 lets you add the nameplates within Columns A and B and apply each column’s percentage separatelyAdd the results to the Column C demand for the larger appliances
7Branch circuits: Note 4 lets one cooktop plus up to two wall ovens in the same room be treated as one rangeAdd the nameplates, then use the table as if it were a single range

Our own summary of the 2023 NEC, not the code text. Look up Tables 220.55 and 220.56 and their notes in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice.

Worked example 1 — single household ranges

Input / stepValueSource
12 kW range, one appliance8 kW demandTable 220.55, Column C
14 kW range: kW above 122 kW14 − 12
Note 1 increase2 × 5% = 10%Table 220.55, Note 1
14 kW range demand8 × 1.10 = 8.8 kWColumn C, adjusted
At 240 V8,800 ÷ 240 ≈ 36.7 ACarry to the service calc

Worked example values only. Look up the other rows and columns in the free NFPA viewer.

Worked example 2 — cooktop + wall oven on one branch circuit

Input / stepValueSource
Counter-mounted cooktop6 kW nameplateSubmittal
Wall oven, same kitchen4 kW nameplateSubmittal
Combined as one range10 kWTable 220.55, Note 4
Branch-circuit demand8 kW (a 10 kW “range” falls under Column C)Table 220.55, Column C
Result8,000 ÷ 240 ≈ 33.3 A → a 40 A circuitCheck ampacity and terminal ratings

Worked example values only. Many designers simply run separate circuits at nameplate — both are acceptable.

Worked example 3 — restaurant kitchen, six pieces of thermostatic equipment

Input / stepValueSource
Connected load (fryers, ovens, griddle, booster heater, etc.)60 kW total, six unitsEquipment schedule
Demand factor for six or more units65%Table 220.56
Demand load60 × 0.65 = 39 kW
Floor check: two largest units15 kW + 12 kW = 27 kW220.56
Kitchen equipment load used39 kW (greater of the two)220.56

Worked example values only. Hood fans, HVAC, and space heating are excluded from Table 220.56 — calculate them separately.

Which cooking rule applies?

SituationRuleNotes
Ranges, cooktops, and ovens in dwelling units220.55 / Table 220.55Also used for household appliances in instructional programs
Commercial cooking, booster heaters, and other thermostatic or intermittent kitchen equipment220.56 / Table 220.56Never less than the two largest loads combined
Single-family dwelling using the optional method220.82Ranges go in at nameplate with the other loads; the optional method applies its own demand
Apartment buildings using the optional method220.84See the multifamily optional method guide
Small fastened-in-place appliances (disposals, dishwashers) in dwellings220.53Separate from the cooking calc

Our own summary of the 2023 NEC, not the code text. Look up Tables 220.55 and 220.56 and their notes in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice.

Common mistakes

MistakeWhat to do instead
Running ranges over 12 kW straight from Column CApply Note 1 first
Applying Table 220.55 to a restaurantCommercial kitchens use 220.56
Including the hood exhaust fan in the 220.56 countHVAC and ventilation are excluded; add them separately
Stopping at the 220.56 percentageCompare to the sum of the two largest pieces and use the larger
Putting a small wall oven through Column C by habitColumn A or B (a percentage of nameplate) usually gives a smaller, still-compliant number — see Note 3

Our own summary of the 2023 NEC, not the code text. Look up Tables 220.55 and 220.56 and their notes in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ. Not engineering advice.

📋 Embed this chart on your site — freeGet the code →

Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.

<iframe src="https://www.field-pm.com/embed/charts/nec-cooking-appliance-demand" title="Cooking Appliance Demand (NEC 220.55/220.56) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe>
<p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nec-cooking-appliance-demand" target="_blank" rel="noopener">Cooking Appliance Demand (NEC 220.55/220.56)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>

Ranges and kitchens without oversizing the service

Look up Tables 220.55 and 220.56 in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how the tables and notes work; it does not reproduce them. Written to the 2023 NEC — verify against the edition your AHJ has adopted.

Household cooking — the columns. Table 220.55 is entered with the number of appliances. Smaller appliances use Column A or B, which are percentages of nameplate; ranges up to 12 kW use Column C, which is a flat kW demand. That is why a 12 kW range goes into the service calc at 8 kW, not 12.

The notes do the real work. Note 1 bumps Column C up by a fixed percentage for each kW a range exceeds 12 kW. Note 2 handles a group of unequal large ranges by averaging them. Note 3 lets you add nameplates within Columns A and B. Note 4 covers branch circuits, letting a cooktop and up to two wall ovens in the same room be treated as a single range. Note 5 carries the same method to household appliances in instructional programs.

Commercial kitchens use 220.56. Thermostatic and intermittent kitchen equipment — fryers, ovens, griddles, dishwasher booster heaters — is totaled and multiplied by a demand factor that shrinks as the number of units grows. The result has a floor: it can never be less than the two largest pieces of equipment added together. Ventilation, HVAC, and space heating stay out of this calc.

Cooking loads drop into the larger service calculation — start with the general lighting load, and for apartment buildings see the multifamily optional method. Size the range circuit with the NEC 310.16 ampacity chart and the standard breaker sizes guide, confirm the receptacle rating with the receptacle rating rules, and put it on the panel schedule.

FAQ

How do I calculate the demand load for an electric range?+

For one household range up to 12 kW, NEC Table 220.55 Column C gives 8 kW. For larger ranges, Note 1 raises that value 5% for each kW above 12. Other appliance counts and sizes are in the table — look it up in the free NFPA viewer at nfpa.org/freeaccess.

Can a cooktop and wall oven share one circuit?+

Yes. Note 4 to Table 220.55 allows a counter-mounted cooktop and up to two wall-mounted ovens in the same room, on one branch circuit, to be added together and treated as one range for the branch-circuit calculation.

When do I use Column A or B instead of Column C?+

Columns A and B cover smaller household cooking appliances and apply a percentage to the nameplate rating. Column C covers appliances up to 12 kW and gives a fixed kW demand. Note 3 explains how to combine them.

How does the commercial kitchen demand factor work?+

Under 220.56, the total connected load of thermostatically controlled or intermittent kitchen equipment is multiplied by a factor based on the number of units — six or more units are taken at 65%. The result can never be less than the two largest pieces added together. HVAC and ventilation are not included.

Did the 2023 NEC change the cooking tables?+

The section numbers 220.55 and 220.56 stayed the same through the 2023 reorganization of Article 220, and the column-and-note method is the same. Wording in the notes does get revised, so read the edition your AHJ enforces.