NFPA 70E 130.4(E) · Approach boundaries
Limited vs restricted approach, movable vs fixed parts, AC vs DC, and how the arc flash boundary fits in — with a worked 480 V example and a free link to the official tables.
Need the actual tables? Look up NFPA 70E Tables 130.4(E)(a) and (b) in the free NFPA viewer →
| Boundary | Hazard | Where the distance comes from | Who may cross it |
|---|---|---|---|
| Arc flash boundary | Arc flash (burns from thermal energy) | Incident energy analysis, or the PPE category tables for listed equipment | Anyone crossing wears arc-rated PPE for the hazard |
| Limited approach boundary | Shock | Table 130.4(E)(a) AC / (E)(b) DC, by voltage | Qualified persons; unqualified only if escorted and advised by a qualified person |
| Restricted approach boundary | Shock — increased likelihood of contact | Same tables, by voltage | Qualified persons only, with shock PPE and a plan to avoid contact |
Our own summary, not the standard text. Look up Tables 130.4(E)(a) and 130.4(E)(b) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NFPA 70E edition your employer and AHJ follow. Not engineering or legal advice.
| Step | What you do | Watch out for |
|---|---|---|
| 1 | Pick the table: (a) for AC systems, (b) for DC systems | Battery rooms, PV, and UPS DC buses use the DC table |
| 2 | Find the nominal voltage range — phase-to-phase for AC | Use system voltage, not voltage to ground (480Y/277 V is a 480 V system) |
| 3 | Choose the limited approach column: "exposed movable conductor" or "exposed fixed circuit part" | Movable means overhead lines or anything that can swing — the distance is much larger |
| 4 | Read the restricted approach boundary in the last column | At the lowest voltage ranges the table says to avoid contact instead of giving a distance |
| 5 | Separately determine the arc flash boundary | It is not in this table — it comes from the equipment label, an incident energy study, or the PPE category table |
| 6 | Apply whichever boundary is farther out first when setting up barricades and attendants | At many 480 V jobs the arc flash boundary is farther out than the limited approach boundary |
Our own summary, not the standard text. Look up Tables 130.4(E)(a) and 130.4(E)(b) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NFPA 70E edition your employer and AHJ follow. Not engineering or legal advice.
| Input / step | Result | Source |
|---|---|---|
| System | 480Y/277 V, 3-phase | Nameplate |
| Voltage range used | The range that contains 480 V | Table 130.4(E)(a) |
| Limited approach — fixed circuit part (bus, terminals) | 3 ft 6 in | Table 130.4(E)(a) |
| Restricted approach | 1 ft 0 in | Table 130.4(E)(a) |
| Arc flash boundary | From the equipment label or study — not this table | 130.5 |
| Setup | Barricade at the larger of the arc flash and limited approach boundaries; only qualified workers inside | 130.4, 130.5, 130.7 |
Worked example values only. Look up the full tables in the free NFPA viewer.
| Mistake | What to do instead |
|---|---|
| Using the fixed-part distance near overhead or temporary movable conductors | Use the movable-conductor column — it is several times larger |
| Treating the arc flash boundary as one of the shock boundaries | They are independent — determine both and respect whichever is farther |
| Using voltage to ground (277 V) to enter the table on a 480Y/277 V system | Enter at the system voltage |
| Letting an apprentice or helper inside the limited approach boundary unescorted | Unqualified persons need a qualified escort who has advised them of the hazards |
| Assuming "de-energized" because the breaker is off | Boundaries apply until an electrically safe work condition is established and verified (LOTO + test) |
Our own summary, not the standard text. Look up Tables 130.4(E)(a) and 130.4(E)(b) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NFPA 70E edition your employer and AHJ follow. Not engineering or legal advice.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/nfpa-70e-approach-boundaries" title="NFPA 70E Approach Boundaries (130.4(E)) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nfpa-70e-approach-boundaries" target="_blank" rel="noopener">NFPA 70E Approach Boundaries (130.4(E))</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Look up Tables 130.4(E)(a) and (b) in the free NFPA viewer. NFPA offers read-only access to the current edition of NFPA 70E at no cost. This page explains how to use the tables; it does not reproduce them.
Picture circles drawn around an exposed energized part. The limited approach boundary is the outer shock line — inside it, a person could get close enough to contact something energized. The restricted approach boundary is the inner shock line, where accidental movement could put a body part or tool in contact. Both distances come from the voltage tables, with separate tables for AC and DC. The limited approach boundary has two columns: a large distance for movable conductors (overhead lines, conductors that can sway) and a smaller one for fixed circuit parts like bus and terminals.
The arc flash boundary is a different animal: it is the distance at which the incident energy from an arc drops to the level that causes a second-degree burn on bare skin. It depends on available fault current and clearing time, not just voltage, so it comes from the equipment label (incident energy analysis) or from the PPE category method. See our guide to NFPA 70E PPE categories for how that works.
Worked example. A qualified electrician is troubleshooting a 480Y/277 V panel with the dead front off. Enter the AC table at 480 V (the system voltage, not 277 V). The limited approach boundary to the fixed bus is 3 ft 6 in and the restricted approach boundary is 1 ft 0 in. The arc flash boundary comes off the panel’s label. The helper stays outside the larger of the two unless escorted — and never crosses the restricted line.
Qualified vs unqualified. A qualified person has the training to recognize and avoid the hazards of that specific equipment and task — it is task-specific, not a job title. Put the boundaries, the energized work permit, and the job briefing on your electrical JSA template. For overhead lines near cranes and equipment, the OSHA rules apply too — see the crane power line clearance chart. Field PM keeps JSAs, permits, and toolbox talks with the job so the record is there when it is needed.
For an exposed fixed circuit part on a 480 V AC system, NFPA 70E Table 130.4(E)(a) gives 3 ft 6 in. The distance for an exposed movable conductor (like an overhead line) is much larger. Look up the full table in the free NFPA viewer at nfpa.org/freeaccess.
For a 480 V AC system the restricted approach boundary in Table 130.4(E)(a) is 1 ft 0 in. Only qualified persons wearing shock protection, with a plan to avoid contact, may cross it.
No. The limited and restricted approach boundaries protect against shock and come from the voltage tables in 130.4(E). The arc flash boundary protects against burns and comes from an incident energy analysis or the PPE category tables in 130.7(C)(15). At 480 V the arc flash boundary is often the larger of the two.
Only when a qualified person has advised them of the hazards and continuously escorts them. An unqualified person may never cross the restricted approach boundary.
The old prohibited approach boundary was removed in the 2015 edition, leaving the limited and restricted boundaries. The table structure has been stable since, but always read the edition your employer has adopted — 70E is revised on a three-year cycle.
Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.
Start free trial →