NEC 250.102(C)(1) · Bonding jumpers · 2023 NEC

How to size supply-side bonding jumpers with NEC Table 250.102(C)(1)

Main bonding jumpers, system bonding jumpers, supply-side bonding jumpers, and the minimum service neutral — what the table sizes, the 12.5% rule past its top row, and how it differs from 250.66 and 250.122.

Need the actual table? Look up Table 250.102(C)(1) in the free NFPA viewer →

Which conductors are sized from Table 250.102(C)(1)?

ConductorWhere it isRule that sends you to the table
Main bonding jumper (MBJ)Neutral bar to enclosure at the service disconnect250.28(D)(1)
System bonding jumperNeutral to enclosure at a separately derived system (transformer, generator)250.28(D)(1), 250.30(A)(1)
Supply-side bonding jumper (SSBJ)Line side of the service or SDS disconnect: raceways, enclosures, bonding bushings, the "ground" in an SDS secondary250.102(C), 250.30(A)(2)
Minimum grounded (neutral) conductorService neutral, even if the calculated neutral load is small250.24(C)(1)
Minimum neutral of a separately derived systemTransformer secondary neutral run to the first disconnect250.30(A)(3)

Our own summary of the 2023 NEC, not the code text. Look up Table 250.102(C)(1) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

How to read Table 250.102(C)(1), step by step

StepWhat you doWatch out for
1Find the largest ungrounded (phase) supply conductor on the line sideSize from the phase conductors — never from the breaker rating
2For parallel sets, add the circular-mil area of one phaseOne phase only, not all phases combined
3Pick the column that matches the phase-conductor material (copper or aluminum)Mixed materials: work in equivalent area (table note)
4If the phase size is within the table, read across to the jumper size in the material you are installingCopper and aluminum jumpers differ for the same row
5If the phase size is past the table's top row, use the percentage rule in the table noteThe jumper keeps growing — unlike a GEC, it has no cap
6For parallel raceways, size one SSBJ per raceway from the conductors in that raceway (250.102(C)(2))Or run a single jumper sized from the total, if it is one jumper for all

Our own summary of the 2023 NEC, not the code text. Look up Table 250.102(C)(1) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

Worked example — 1200 A service, three parallel sets of 500 kcmil copper

Input / stepValueSource
Conductors per phase3 × 500 kcmil CuDesign
Equivalent area of one phase1500 kcmil3 × 500
Past the table's copper top row?Yes — above 1100 kcmilTable 250.102(C)(1), note
12.5% of the equivalent area187.5 kcmil0.125 × 1500
Next standard size at or above 187.5 kcmil4/0 AWG Cu (211.6 kcmil)Chapter 9, Table 8
Main bonding jumper / single SSBJ / minimum neutral4/0 AWG CuResult
SSBJ if one run in each of three conduitsSize per conduit from one set of 500 kcmil250.102(C)(2)
Compare: GEC for the same service3/0 AWG CuTable 250.66 top row

Worked example values only. Look up the full table in the free NFPA viewer.

250.66 vs 250.102(C)(1) vs 250.122 — which table?

TableSizesBased onGrows without limit?
250.66Grounding electrode conductorLargest ungrounded service/SDS conductorNo — the table tops out
250.102(C)(1)MBJ, system bonding jumper, SSBJ, minimum service neutralLargest ungrounded supply conductorYes — percentage rule past the top row
250.122Equipment grounding conductor and load-side bonding jumperRating of the OCPD ahead of itFollows the OCPD size

Our own summary of the 2023 NEC, not the code text. Look up Table 250.102(C)(1) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

Common field mistakes

MistakeWhat to do instead
Using the GEC size for the main bonding jumperThe GEC stops growing at the top of 250.66; the MBJ keeps growing under the 12.5% rule
Sizing the SSBJ from Table 250.122250.122 is for load-side EGCs and bonding jumpers. Line side goes to 250.102(C)(1)
Running a small neutral because the calculated neutral load is low250.24(C)(1) sets a floor: the service neutral must carry fault current back to the source
Sizing a transformer SSBJ from the primary conductorsSize from the secondary (derived) phase conductors
Rounding 12.5% down to the nearest sizeAlways go up to the next standard size with at least that area
One tiny jumper per conduit sized from the totalPer-raceway jumpers are sized from that raceway's conductors; one common jumper is sized from the total

Our own summary of the 2023 NEC, not the code text. Look up Table 250.102(C)(1) in the free NFPA viewer (nfpa.org/freeaccess) and verify against the NEC edition adopted by your AHJ.

📋 Embed this chart on your site — freeGet the code →

Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.

<iframe src="https://www.field-pm.com/embed/charts/nec-supply-side-bonding-jumper-sizing" title="Bonding Jumpers & SSBJ (NEC 250.102(C)(1)) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe>
<p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/nec-supply-side-bonding-jumper-sizing" target="_blank" rel="noopener">Bonding Jumpers & SSBJ (NEC 250.102(C)(1))</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>

Line-side bonding, explained

Look up Table 250.102(C)(1) in the free NFPA viewer. NFPA offers read-only access to current NEC editions at no cost. This page explains how to use the table; it does not reproduce it.

On the line side of a service or transformer secondary disconnect there is no overcurrent device protecting the conductors, so a bonding jumper there can’t be sized by a breaker rating. Instead, Table 250.102(C)(1) sizes it from the largest ungrounded supply conductor. The same table sets the main bonding jumper, the system bonding jumper at a separately derived system, and the minimum size of the service neutral — because on the line side, the neutral is the fault-return path to the source.

The 12.5% rule. The table covers phase conductors up to a top row (1100 kcmil copper, 1750 kcmil aluminum). Past that, a table note requires the jumper to have at least 12.5% of the area of the largest phase conductor, or the equivalent area of a parallel set. That’s the key difference from the grounding electrode conductor table (250.66), which stops growing at its top row: the GEC only has to carry current to earth, while a bonding jumper must carry the full available fault current back to the source.

Worked example. A 1200 A service runs three parallel sets of 500 kcmil copper — 1500 kcmil per phase, which is past the top row. 12.5% of 1500 is 187.5 kcmil. The next standard size with at least that area is 4/0 AWG copper (211.6 kcmil), so that’s the minimum main bonding jumper, the minimum service neutral, and the size of a single SSBJ serving all three conduits. The GEC for the same service tops out at 3/0 copper. If you bond each conduit with its own jumper instead, 250.102(C)(2) lets you size each one from the 500 kcmil set in that conduit.

Once you are past the disconnect, switch tables: load-side bonding jumpers and EGCs follow the OCPD rating — see the equipment grounding conductor chart (NEC 250.122). Size the phase conductors themselves with the NEC 310.16 ampacity chart. Field PM keeps grounding and bonding inspections, photos, and as-builts with the job file.

Not engineering advice. Edition note: this page follows the 2023 NEC. Table 250.102(C)(1) arrived in the 2017 edition; older editions sized these jumpers by referring to Table 250.66 plus the same percentage rule, so older textbooks may point you to the wrong table. Verify the edition your AHJ enforces.

FAQ

How do I size a supply-side bonding jumper?+

Find the largest ungrounded supply conductor on the line side (totaling one phase for parallel sets), and look up that size in the matching material column of NEC Table 250.102(C)(1). If it is past the table's top row, the jumper must be at least 12.5% of the phase conductor area, rounded up to a standard size. Look up the table in the free NFPA viewer at nfpa.org/freeaccess.

What is the 12.5% rule?+

When the ungrounded conductors exceed the table's top row (above 1100 kcmil copper or 1750 kcmil aluminum), the bonding jumper or minimum grounded conductor must have at least 12.5% of their area. Example: three sets of 500 kcmil copper is 1500 kcmil per phase; 12.5% is 187.5 kcmil, which rounds up to 4/0 AWG copper.

Is the main bonding jumper the same size as the grounding electrode conductor?+

Often on smaller services, but not always. The GEC table (250.66) has a top row and stops growing, while Table 250.102(C)(1) keeps growing through the 12.5% rule. On large parallel services the main bonding jumper ends up larger than the GEC.

Why does the service neutral have a minimum size?+

Because on a service the neutral is the path fault current takes back to the utility transformer. Section 250.24(C)(1) requires it to be at least the Table 250.102(C)(1) size even if the calculated neutral load would allow something smaller.

When do I use 250.122 instead?+

On the load side of the service or separately derived system disconnect. Equipment grounding conductors and load-side bonding jumpers are sized by the overcurrent device rating in Table 250.122. Line-side bonding stays with Table 250.102(C)(1).

Built by a contractor, for the field

Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.

Start free trial →

More reference charts

Rated by contractors on

Field PM reviews on CapterraField PM reviews on GetAppField PM reviews on Software Advice