IPC 604.3 · 604.4 · Water supply sizing
Fixture pressure and flow criteria, maximum flow rates, water supply fixture units, and the pressure-loss (friction budget) method — with worked examples and a free link to the official tables.
Need the actual tables? Read IPC Section 604 and Appendix E free at codes.iccsafe.org →
| Table / section | What it tells you | When you use it |
|---|---|---|
| Table 604.3 | The minimum flow and the minimum flowing pressure each fixture needs at its supply outlet | Sets the pressure you must still have at the most demanding fixture after all losses |
| Table 604.4 | The maximum flow rate or flush volume allowed for faucets, showerheads, water closets, and urinals | Water-conservation limits — also why modern demand is lower than the old tables assumed |
| 604.5 | Minimum size of the individual fixture supply pipe | The short pipe from the branch to each fixture |
| 604.8 | When a pressure-reducing valve is required | High street or well pressure |
| Appendix E (WSFU tables) | Fixture-unit values per fixture and a conversion from total fixture units to design flow (gpm) | Turning a list of fixtures into a peak demand |
| Appendix E friction-loss charts | Pressure loss per 100 ft for each pipe material and size at a given flow | Picking the pipe size that fits your friction budget |
Our own summary, not the code text. Read IPC Section 604 and Appendix E free at codes.iccsafe.org (2021/2024 IPC) and verify against the edition adopted by your AHJ. Not engineering advice — larger systems are designed by a licensed engineer.
| Step | What you do | Watch out for |
|---|---|---|
| 1 | List every fixture, assign its water supply fixture units (WSFU), and total them for each pipe section | Private and public fixtures carry different values; hot and cold are listed separately from the combined value |
| 2 | Convert total WSFU to design flow in gpm using the Appendix E demand table | Flush-tank and flushometer systems use different curves |
| 3 | Start from the minimum static pressure at the main (ask the water utility) | Use the low-season, low-pressure figure, not a single gauge reading |
| 4 | Subtract elevation: 0.433 psi for every foot the highest fixture sits above the main | That is physics, not code — it applies to every system |
| 5 | Subtract the meter, backflow preventer, softener, and filter losses at design flow (manufacturer data) | Reduced-pressure backflow assemblies can eat a big share of the budget |
| 6 | Subtract the minimum flowing pressure the most demanding fixture needs (Table 604.3) | The highest fixture is not always the most demanding one |
| 7 | What is left is the friction budget. Divide it by the equivalent length (developed length plus an allowance for fittings) and express it per 100 ft | Appendix E notes a common rule of adding about half again to developed length for fittings |
| 8 | Pick the smallest pipe whose friction loss at design flow stays under the budget and whose velocity stays within your design limit | Velocity limits protect copper from erosion and cut water hammer |
Our own summary, not the code text. Read IPC Section 604 and Appendix E free at codes.iccsafe.org (2021/2024 IPC) and verify against the edition adopted by your AHJ. Not engineering advice — larger systems are designed by a licensed engineer.
| Input / step | Value | Source |
|---|---|---|
| Minimum static pressure at the main | 60 psi | Utility (assumed) |
| Highest fixture 25 ft above the main | − 10.8 psi | 25 × 0.433 |
| Meter loss at design flow | − 6 psi | Manufacturer curve (assumed) |
| Backflow preventer loss at design flow | − 12 psi | Manufacturer curve (assumed) |
| Minimum pressure at the highest flushometer fixture | − 15 psi | Appendix E example value for flushometer valves |
| Friction budget | 16.2 psi | 60 − 10.8 − 6 − 12 − 15 |
| Developed length 120 ft × 1.5 fitting allowance | 180 ft equivalent | Appendix E rule of thumb |
| Allowable friction | ≈ 9.0 psi per 100 ft | 16.2 × 100 ÷ 180 |
| Next | Find the design gpm from total WSFU, then the smallest pipe on the friction chart at or under 9.0 psi/100 ft | Appendix E |
Worked example values only (assumed site data). Read Section 604 and Appendix E free at codes.iccsafe.org.
| Input / step | Value | Source |
|---|---|---|
| Fixture | Water closet, flush tank, private use | Fixture schedule |
| Combined WSFU for that fixture | 2.2 | Appendix E fixture-unit table |
| Two of them on one branch | 4.4 WSFU | 2 × 2.2 — add the other fixtures on the branch the same way |
Worked example value only. Use the combined column for cold-plus-hot piping and the separate columns for hot-only or cold-only sections.
| Mistake | What to do instead |
|---|---|
| Adding fixture gpm straight across ("everything open at once") | Convert total WSFU to demand — fixture units account for the odds of fixtures running together |
| Forgetting the backflow preventer loss | Get the loss at design flow from the assembly’s flow curve; it often decides the pipe size |
| Sizing to the gauge reading on a Sunday morning | Use the utility’s minimum static pressure |
| Picking the size by friction only | Check velocity too — undersized copper at high velocity erodes and bangs |
| Leaving high pressure unregulated | Where static pressure exceeds the 604.8 limit, install a pressure-reducing valve |
| Assuming older fixture flows | Table 604.4 caps flow rates, and modern low-flow fixtures lower real demand — the UPC’s Water Demand Calculator exists for that reason |
Our own summary, not the code text. Read IPC Section 604 and Appendix E free at codes.iccsafe.org (2021/2024 IPC) and verify against the edition adopted by your AHJ. Not engineering advice — larger systems are designed by a licensed engineer.
Paste this where you want the live chart to appear. It works on any site that allows iframes, and includes a link back to Field PM.
<iframe src="https://www.field-pm.com/embed/charts/water-supply-pipe-sizing-explained" title="Water Supply Pipe Sizing (IPC 604 & WSFU) — Field PM" width="100%" height="620" loading="lazy" style="border:1px solid #e5e7eb;border-radius:12px;max-width:560px;width:100%"></iframe> <p style="font:13px/1.5 system-ui,sans-serif;margin:8px 0;color:#6b7280"><a href="https://www.field-pm.com/charts/water-supply-pipe-sizing-explained" target="_blank" rel="noopener">Water Supply Pipe Sizing (IPC 604 & WSFU)</a> by <a href="https://www.field-pm.com" target="_blank" rel="noopener">Field PM</a></p>
Read Section 604 and Appendix E free on codes.iccsafe.org. ICC offers free read-only access to the 2021 and 2024 International Plumbing Code. This page explains the method; it does not reproduce the tables.
Water pipe sizing is a pressure budget. You start with what the utility guarantees at the main, spend some of it lifting water to the top floor, spend more on the meter and backflow preventer, and hold back what the worst fixture needs to work (Table 604.3). Whatever is left is the pressure you can afford to lose to pipe friction — and that decides the pipe size.
Demand comes from fixture units, not from adding gpm. Each fixture carries a water supply fixture unit (WSFU) value. Total them per pipe section and convert the total to a design flow; the conversion bakes in the odds that fixtures run at the same time. Table 604.4 caps how much each fixture may flow, which is why buildings full of low-flow fixtures use less water than the old demand curves predicted.
Worked example. With 60 psi at the main, the top fixture 25 ft up (10.8 psi), 6 psi through the meter, 12 psi through the backflow preventer, and 15 psi held back for a flushometer, the friction budget is 16.2 psi. Over 120 ft of pipe plus a 50% fitting allowance (180 ft), that is about 9 psi per 100 ft — pick the smallest pipe that stays under it at design flow without exceeding your velocity limit.
Western jurisdictions on the Uniform Plumbing Code (IAPMO) size water piping under UPC Chapter 6 and Appendix A, and many allow the Water Demand Calculator in UPC Appendix M for dwellings. The idea is the same, but the fixture-unit values and demand curves differ — do not mix the two codes.
For tube dimensions and wall types see the copper tube size chart and the steel pipe schedule chart. The drain side is covered in drainage fixture units and pipe sizing, and support spacing in pipe hanger spacing. Field PM keeps submittals, pressure-test records, and inspection photos with the job.
A WSFU is a load factor that rates how much a fixture contributes to peak demand, based on its flow, how long it runs, and how often it is used. You total the WSFU on each pipe section and convert the total to a design flow in gpm; the conversion accounts for the fact that not every fixture runs at once. The values are in IPC Appendix E, readable free at codes.iccsafe.org.
Table 604.3 is the minimum — the flow and flowing pressure each fixture needs to work. Table 604.4 is the maximum — the most water a faucet, showerhead, or flushing fixture is allowed to use. You design so every fixture gets at least its 604.3 pressure while the fixtures themselves meet the 604.4 limits.
A column of water loses 0.433 psi of pressure for every foot of rise. Multiply the height of the highest fixture above the main by 0.433 and subtract it from the available pressure before you work out the friction budget.
IPC 604.8 requires an approved pressure-reducing valve where the static pressure inside the building would exceed its limit. Check your edition for the exact threshold and the strainer and bypass requirements that go with it.
Jurisdictions on the Uniform Plumbing Code (IAPMO, common in the western US) size water piping under UPC Chapter 6 and Appendix A, with their own fixture-unit values. For single- and multi-family dwellings, UPC Appendix M allows the IAPMO Water Demand Calculator, a statistical method built for low-flow fixtures. Consult the UPC edition your jurisdiction adopted.
Field PM runs daily reports, job costing, QA/QC, and billing in one platform — $99/month with unlimited foremen, QA/QC, and safety free. 30-day trial, no credit card.
Start free trial →