Free I&E template · Excel

Free Loop Check Sheet & Calibration Record

Prove every instrument loop from the field device to the operator screen. Wiring and insulation, 5-point signal injection with the mA and % span math built in, alarms and interlocks, valve stroke and fail position, and three-party sign-off.

  • Wiring, continuity, shield & insulation resistance checks
  • 5-point injection: expected mA = 4 + 16 × %, HMI reading
  • Error % of span vs. your tolerance → PASS / FAIL
  • Alarms, trips & interlocks with trip error
  • Valve stroke, fail position, limit switches
  • Loop check log with overdue flag and % complete
  • Calibration record: as-found / as-left, standard cal due, next due

Loop Check Sheet

We'll email you a copy + send the file to your browser right now.

Excel (.xlsx) · works in Excel, Google Sheets, Numbers

Want it with your logo on it?

A free account puts your logo, company info, and license # on every template, and adds one-click template packs. Free forever, even after the trial.

Get branded templates free →

By downloading you agree to receive occasional Field PM updates. Unsubscribe anytime. We don't share your email — read our privacy policy.

What's inside the workbook

Pre-formatted, print-ready, with embedded Field PM branding. Works in Excel, Google Sheets, and Numbers.

01

Loop Check Sheet

One loop per sheet: wiring and insulation, 5-point signal injection with calculated expected mA and % span error, alarms and interlocks, final element, overall result and sign-offs.

02

Loop Check Log

Every loop with planned date, status, tech and witness. Counts by status, % complete, client accepted and overdue.

03

Calibration Record

5-point as-found / as-left with error % of span, pass / fail against tolerance, test standard traceability and next cal due date.

04

Instructions

Step-by-step for each section, from prerequisites to punch and re-check.

Want this automated?

Stop re-typing the same form on every job.

Field PM has this exact form built in — crews fill it out from a phone, the data flows into the project record, and you get a clean PDF for the GC or owner with one click. No re-typing, no lost paperwork, no missed signatures.

30 days free · no credit card · every feature unlocked from day one.

Paper / Excel

  • ✗ Hand-writes the form on the jobsite
  • ✗ Re-types into Excel at the trailer
  • ✗ Emails the PDF back to the office
  • ✗ No audit trail, no signatures
  • ✗ Data never feeds payroll or the budget

Field PM

  • ✓ Fill out from a phone in under 3 min
  • ✓ Photos, signatures, and audit log built in
  • ✓ One-click PDF for the GC and owner
  • ✓ Data feeds payroll, budget, and reports
  • ✓ Replaces 5 forms with one platform

On your phone & tablet

Every template — in the app, in your pocket

This template and every other one is built into the Field PM app. Fill them out right from the jobsite on any iPhone, iPad, or Android — photos, signatures, and a clean GC-ready PDF included. Download free:

Download on theApp StoreGet it onGoogle Play

Frequently asked questions

What is an instrument loop check?

A loop check proves that a complete instrument loop works end to end — field device, wiring, junction boxes, marshalling, I/O card, control-system configuration and HMI display — before the process is started. The technician injects or simulates known values across the range and confirms the control system reads them correctly, then verifies alarms, trips and the final element.

How do you calculate the expected mA at each test point?

For a 4-20 mA signal, expected mA = 4 + 16 × (% of span). So 0% = 4 mA, 25% = 8 mA, 50% = 12 mA, 75% = 16 mA and 100% = 20 mA. The template calculates it for each row and compares the measured mA and the HMI reading against it.

How is error % of span calculated?

Error % of span = (reading − expected) ÷ span. For milliamps the span is 16 mA; for the HMI it is the calibrated range (URV − LRV). A 0–2,500 BPD transmitter reading 1,252 at the 50% point (1,250 expected) is off by 2 ÷ 2,500 = 0.08% of span. The sheet marks PASS when the error is within your tolerance input.

What is the difference between a loop check and a calibration?

Calibration sets and proves the instrument itself — as-found, adjust, as-left against a traceable standard. A loop check proves the whole signal path from the device to the operator screen, including wiring, configuration, alarms and interlocks. Most projects calibrate (or bench-verify) first, then loop check. This workbook has both.

What tolerance should I use?

Use the tolerance in your project instrument specification or the client's commissioning procedure. It differs by service — custody-transfer and safety-instrumented loops are usually tighter than local indication. The template leaves tolerance as an input rather than assuming one.

A loop check record that proves the whole signal path

A loop check confirms that the transmitter, wiring, junction boxes, marshalling, I/O card, configuration and HMI all agree — before the process sees it. This free template walks the technician through each section and does the 4-20 mA and % of span math, so the result is consistent from tech to tech and loop to loop.

Track every loop on the log tab and keep instrument calibrations on the calibration record tab. Build your loop list from the instrument index & I/O list template so ranges and setpoints match.

Field PM moves loop checks, hold points and client sign-offs onto the phone, with photos, e-signatures and automatic filing into the job book.

How to run an instrument loop check that holds up at turnover

The loop check is where an I&E job gets proven. Every transmitter, switch and valve has been installed, tubed, pulled, terminated and megged — and none of that matters until the tech at the device and the operator at the screen agree on what the number is. A good loop check record is also what the client's commissioning team, your QC manager and, if something goes wrong a year later, an investigator will look at. The free workbook above gives you the check sheet, a log to track every loop, and a calibration record, with the math done for you.

Before you start: what has to be done first

  • Device installed and hooked up per the install detail, with tubing pressure-tested and the process connection isolated or in a safe state.
  • Terminated both ends and the terminations checked — see the termination wire list template.
  • Calibrated or bench-verified to the range on the instrument index.
  • I/O card live and the tag configured in the PLC, DCS or SIS, with the HMI graphic available.
  • Documents in hand: loop drawing, datasheet, alarm/trip schedule or cause-and-effect, and the permit for the work.

Section A — wiring, continuity and insulation

Ring out each conductor from the device to the field junction box and on to the marshalling terminals. Confirm the wire tags and ferrules match the drawing, polarity is right, and the shield is grounded at one end only (normally the panel end) and cut back and taped at the field end. Ground loops from shields landed at both ends are one of the most common causes of noisy 4-20 mA signals.

Insulation resistance: lift the conductors at the I/O card and disconnect the transmitter before you put a megger on the cable. An insulation tester will destroy loop-powered electronics and I/O channels. Use the test voltage your project spec calls for; our insulation resistance testing reference covers how readings are interpreted.

Section B — 5-point signal injection

Apply 0, 25, 50, 75 and 100% of the calibrated range at the process connection (pressure source, simulator) or simulate the output from the transmitter with a HART communicator. At each point record:

ColumnHow it works
Applied valueLRV + % × (URV − LRV), in engineering units. Calculated.
Expected mA4 + 16 × %. Calculated.
Measured mAWhat your meter reads at the I/O terminals.
mA error % span(measured − expected) ÷ 16. Calculated.
HMI readingWhat the operator screen shows.
HMI error % span(HMI − applied) ÷ span. Calculated.
ResultPASS when both errors are within ± your tolerance.

If the mA is right and the HMI is wrong, the problem is configuration — range, scaling or units in the controller. If the mA is wrong, it's the device or the wiring. Recording both is what lets you tell the difference on paper.

Section C — alarms, trips and interlocks

Drive the signal through each alarm and trip setpoint from the alarm schedule or cause-and-effect chart and record where it actually tripped. Then prove the action: the HMI alarm annunciates and logs, the pump stops, the ESD valve closes, the first-out indication is correct. Check what happens on a bad signal — under-range, over-range, open wire — and that the controller does what the philosophy says. Safety-instrumented trips are usually client-witnessed; get initials on the row.

Section D — final element and fail position

For control valves, command 0-25-50-75-100% and record the travel you actually see; the sheet calculates the deviation against your position tolerance. For every valve, pull the signal and the air and confirm it goes to its fail position (fail closed, fail open, fail last). Time the stroke both ways on on/off and ESD valves and confirm the open and closed limit switches match the HMI.

The loop check log

One line per loop, with planned date, status, tech and client witness. Status moves Not Started → Ready for Check → In Progress → Passed or Failed - Punch → Re-check Passed → Client Accepted. The progress block counts each status and shows % complete, and an overdue flag catches loops past their planned date. Keep failed loops visible with their punch number — the history is part of the record.

The calibration record

Record as-found before you touch anything, then adjust and record as-left, five points each. Error % of span = (measured mA − expected mA) ÷ 16. Enter your test standard and its calibration due date: if the standard was out of cal on the calibration date, the sheet flags the record "OUT OF CAL — results void", because it is. Next due date is calculated from your calibration interval. An as-found failure on an instrument that's been in service is information someone needs — don't adjust it away without writing it down.

Mistakes that cost re-checks

  • Checking the mA and skipping the HMI. Half of loop check failures are scaling or configuration, not wiring.
  • Verifying the alarm but not the action. The alarm banner came up; did the valve close?
  • Megging with the transmitter connected. Expensive, and it happens every job.
  • Signing a loop complete with open items. If a section failed, the overall result says FAIL until it's re-checked.
  • Out-of-date test equipment. A calibrator past its due date undermines every record it touched.

Beyond paper check sheets

Printed check sheets get rained on, lost in a truck and signed a week late. Field PM QA/QC workflows step each loop through wiring, injection, alarms and client acceptance with hold points and e-signatures, and the form library ships with ready-made industrial QC forms. Signed records file into the job book automatically. Start a free 30-day trial.

Related templates

Rated by contractors on

Field PM reviews on CapterraField PM reviews on GetAppField PM reviews on Software Advice